KNX Heat Consumption Measuring Device Heat Meter / NZR
APB
Introduction The Arcus-EDS Heat Meter is a „Dialog WZ-CD / -HY“ Heat Consumption Counter (calibration optional) from the company NZR, with an integrated KNX Bus Interface for remote reading and monitoring. The electronic counter is operated by a lithium battery with a 5-year lifespan and 1-year additional reserve. The KNX bus interface is built into the counter and is connected non-reactively with the external terminal block. The meter with the integrated bus interface is authorized by the Physikalisch Technischen Bundesanstalt (PTB) (German Federal Institute of Physics and Metrology).
Pic. 1 Heat Meter with KNX Connector
Pic. 2 Open KNX Connector Housing
KNX – Interface The following items are available for remote reading with the KNX/EIB System: Nr. 0 1 2 3 4 5 6 7 8
Current Output in kWh/h Accumulated Volume in m3 Flow Temperature in °C Return Temperature in °C Current Flow m3/h Current Consumption Saved Value for Due Date Serial Number Error Message
Current Output Accumulated Volume Flow Temperature Return Temperature Current Flow Current Consumption Saved Value for Due Date Serial Number Error Message
Data Point Type DPT14.056 = Output DPT14.076 = Volume DPT9.001 = Degrees Celsius DPT9.001 = Degrees Celsius DPT14.077 = Volume Flow DPT14.056 = Output DPT14.056 = Output DPT16.000 = String DPT7.001=2 Unsigned Byte
Data Type Measurement 4 Byte Integrator 4 Byte Measurement 2 Byte Measurement 2 Byte Measurement 4 Byte Measurement 4 Byte Integrator 4 Byte Identification 14 Byte System Status 2 Byte
in kWh/h, the current output in the system. in m3, the total amount of flow through water. in °C, the temperature of the water in the system. in °C, the temperature of the water returning to the system. m3/h, the current amount of flow through water. in kWh, the accumulated warmth output. in kWh, the accumulated warmth output for a particular date ( internal value in the meter ). String, for positive identification of the meter. Error Report with Error Code from the manufacturer.
None of the items can be altered from the bus.
Arcus-EDS GmbH, Rigaer Str. 88, 10247 Berlin, Tel.: 0049/30/25933914, Fax: 0049/30/25933915
[email protected] www.arcus-eds.de
610
e11
KNX Heat Consumption Measuring Device Heat Meter / NZR
APB
Parameter: The following settings are available to set the parameters with ETS:
The following is available for all items except Serial Number and Error Number: Periodic Transmission (2min) Transmission - Change No Transmission
The current measurement is transmitted every 2 minutes to the bus. The current measurement is transmitted to the bus only when a change occurs (minimum interval 2 min). The current measurement is not transmitted automatically (Measurements are read manually).
Installation The heat meter must only be installed and put into operation by an authorized specialist. In addition, knowledge of Engineering Tool Software (ETS) is required. Set-up is carried out with ETS Version 2 or higher. You will find the heat meter in ETS under manufacturer: Arcus-eds, Product Family: Meter, Product Type: heat meter. The EIB programming button and programming LED are located on the attached housing. (see above). Technical data for the heat meter can be found in the data sheet of the manufacturer NZR: Technical Documentation Heat Meter Dialog WZ-HY db-wz-cd.pdf / db-wz-hy.pdf (see attached)
Program de-activate and reset sensor: If there is an error in programming and the counter no longer reacts, you can delete the project by pressing the program button. Press the program button down while connecting the EIB bus clamp and wait for the program LED to light up. This takes from 5-10 seconds.
Arcus-EDS GmbH, Rigaer Str. 88, 10247 Berlin, Tel.: 0049/30/25933914, Fax: 0049/30/25933915
[email protected] www.arcus-eds.de
610
e11
KNX Heat Consumption Measuring Device Heat Meter / NZR
APB
Imprint: Publisher: Arcus-EDS GmbH, Rigaer Str. 88, 10247 Berlin Responsible for Content: Hjalmar Hevers, Reinhard Pegelow Reprints, including partial reprints, can be made only with expressed permission from Arcus-EDS GmbH. This information is the best to our knowledge and is without guarantee. We reserve the right to make any technical and price changes at any time. Liability: Selection and determining the appropriateness of the devices for a designated purpose is the customer’s full responsibility. We offer no liability or guarantee for this. The data in the catalogue and data sheets is a result of experienced measurements and does not embody a guarantee of particular features. Arcus excludes responsibility for damage done on the part of the customer due to improper operation/projecting or malfunctions. On the contrary, the operator/projector must ensure that improper operation, and projection and malfunctions do not lead to any further damage. Safety Guidelines: Attention! Installing and assembling electrical devices must only be done by an electronics specialist. The customer should be aware of and adhere to the safety guidelines of VDE, TÜV and the appropriate energy provider. Our guarantee does not include defects and damage caused by improper use or non-compliance of operating instructions. Warranty: We provide a warranty as required by law. Please contact us in case of malfunction and send the device with a full description of the fault to the address below Manufacturer:
Registered Trademarks: The CE Trademark is an unofficial market trademark used exclusively by authorities and provides no warranty of properties. Registered Trademark of Konnex Association
Arcus-EDS GmbH, Rigaer Str. 88, 10247 Berlin, Tel.: 0049/30/25933914, Fax: 0049/30/25933915
[email protected] www.arcus-eds.de
610
e11
Wärmezähler WZ-CD heat meter WZ-CD Beschreibung / Description Rechenwerk / Counter Rechenwerk mit seperater Zulassung bis 180°C / Counter with separate approval up to 180°C
Temperaturdifferenz / Temperature difference: 2 … 130 K Zulassung für asymetrischen Einbau der Temperaturfühler / approval for asymmetric mountains of the temperature sensors
4-Bit Mikrocontroller / 4-bit micro-controller 7-stelliger Multifunktions-LCD / 7-digit multi function LCD
Berührungslose Display-Umschaltung / Non-contact display switching
Rechenwerkgehäuse 355° drehbar / Counter rotateable by 355°
umweltfreundlicher 3 V Lithium-Batterie / ecofriendly 3V lithium battery
Batterielebensdauer 5 Jahre plus 1 Jahr Gangreserve / battery service life 5 years plus 1 year power-reserve
Selbstkalibrierender Temperaturmesskreis / Automatically calibrating temperature range
Menüanzeigen / Menu displays Menü Menu
1
Beschreibung
Dauer
Description
Time
10
Aktueller Verbrauchswert (Anzeige in kWh/MWh möglich) Current consumption value (display in kWh/MWh possible)
2
Seriennummer (6-stellig)
3
Vorjahresverbrauchswert (Verbrauch am Stichtag)
10
Serial number (6-digit)
10
Displaytest / Display test
4
5
Aktuelles Datum / Current date
5
6
12 Monatsendwerte 12 month end value Vorlauftemperatur in °C
Je 6 125
Supply temperature in °C
9
Rücklauftemperatur in °C Return temperature in °C Akkumuliertes Volumen in m³
Kommunikation / Communication Fernauslesbar über / Readable from remote location via: EIB, M-Bus, D-Bus, S0 Volumenteil / Volume device Beliebige Einbaulagen / Any installation positions Überkopfeinbau / Overarm installation Volumenerfassung über elektronische Abtastung (magnetfrei) / Volume recording via electronical sensing (magnet-free) optimal 2-point suspension made of sapphire/carbide metal
4
8
Display
optimale 2-Punkt-Lagerung aus Saphir/Hartmetall /
Consumption value previous year (consumption on cut-off date)
7
Display
125
Temperaturbereich / Temperatur range: Opional Temp.-Bereich / optional temp-range
15 - 90 °C 15 - 120 °C
Temperaturfühler / Temperature sensor Typ / Type: Durchmesser / Diameter: Temperaturbereich / Temperature range: Temperaturdifferenz / Temperature difference: Kabellänge / Cable length:
Pt 500 5,2 mm 3 … 105 °C 2 … 130 K 1.5 m
10
Accumulated volume in m³
10
momentaner Durchfluss
125
current flow rate
11
momentane Leistung
125
Wärmezähler
current power
12 13
Fehleranzeige / Error display
5
Geeicht bis Monat/Jahr /
5
calibrated till month/year
14
hohe Auflösung mit 3 Nachkommastellen
5
high precision with 3 decimal places
15
Impulswertigkeit Rechenwerk [Liter]
5
impulse calculator [liter]
16
Impulswertigkeit Volumenteil [Liter]
5
impulse volume part [liter]
Funktionsanzeigen / Function displays Volumenimpuls
Symbol "Stern" zeigt eingehenden Volumenimpuls an. Symbol "star" shows incoming volume impulse.
Kommunikation
Symbol "Telefon" zeigt Aktualisierung der Netzwerkvariablen an. Symbol "phone" shows updating of network variables.
Gerätewechsel
Symbol "Batterie" zeigt erschöpfte Batteriekapazität an. Symbol "battery" shows low battery capacity..
Stand 10/2007 86
NORDWESTDEUTSCHE ZÄHLERREVISION Ing. Aug. Knemeyer GmbH & Co. KG
Technische Änderungen vorbehalten. www.nzr.de
+49 (0) 54 24 / 29 28 - 0
Wärmezähler WZ-CD heat meter WZ-CD Kommunikationsoptionen
Communication options
Impulsausgang SO (open Kollektor) oder potentialfreier Kontakt Impulswertigkeit: - 1 kWh/Imp bei kWh-Anzeige - 10 kWh/Imp bei MWh-Anzeige
Impulse output SO (open collector) or potential-free contact Impulse value: - 1 kWh/Imp with kWh display - 10 kWh/Imp with MWh display D-Bus interface economical dialogue bus (twin-wire technology) readable data: Serial number, energy value, cut-off date value, volume, flow rate, heating power, supply and return temperature, temperature difference
D-Bus-Schnittstelle kostengünstiger Dialog-Bus (2-Drahttechnik) auslesbare Daten: Seriennummer, Energiewert, Stichtagswert, Volumen, Durchfluss, Wärmeleistung, Vor- und Rücklauftemperatur, Temperaturdifferenz
M-Bus interface integrated M-Bus interface in accordance with. EN 1434-3 readable data: Serial number, energy value, cut-off date value, volume, flow rate, heating power, supply and return temperature, temperature difference
M-Bus-Schnittstelle integrierte M-Bus-Schnittstelle gem. EN 1434-3 auslesbare Daten: Seriennummer, Energiewert, Stichtagswert, Volumen, Durchfluss, Wärmeleistung, Vor- und Rücklauftemperatur, Temperaturdifferenz
EIB interface integrated EIB interface in accordance with. EIB/KNX readable data: Serial number, energy value, cut-off date value, volume, flow rate, heating power, supply and return temperature, temperature difference
Volum enteil / Vo l u m e d evi ce N enndurchflus s / F low rate N ennw eite / Nominal diameter Maxim ale Belas tung / Max imum flow rate D auerbelas tung / Max imum work ing flow rate Trenngrenze / T rans itional flow rate Kleins ter D urchflus s / Minimum flow rate
qp DN qs
m ³/h mm m ³/h
0,6 15 1,2
1,0 15 2
qp
m ³/h
0,6
1,0
1,5
2,5
qt q min
l/h l/h l/h " " mm mm mm
48 12 8 3/4 1/2 110
80 20 11 3/4 1/2 110
120 30 13 3/4 1/2 110
280 70 18 1 3/4 130
85523115 85563115 85533115 85543115 85573115 85623115 85663115 85633115 85643115 85673115
85523125 85563125 85533125 85543125 85573125 85623125 85663125 85633125 85643125 85673125
Anlauf / Starting flow rate Ans chlus s / Conec tion AG Zähler / Meter AG Vers chraubung / Sc rew c onnec tio Ba ulänge / Length L Ba uhöhe / Height H Breite R e chenw erk / W idth E Be stellinform ationen / O r d er l i st WZ für trockene Fühler / for dry s ens ors VMT-C D 90°C m it Im puls / with impuls e VMT-C D 90°C m it D -Bus / with D-Bus VMT-C D 90°C m it M-Bus / with M-Bus VMT-C D 90°C m it EIB / with EIB VMT-C D 90°C WZ für nas s e Fühler / for wet s ens ors VMT-C D 90°C m it Im puls / with impuls e VMT-C D 90°C m it D -Bus / with D-Bus VMT-C D 90°C m it M-Bus / with M-Bus VMT-C D 90°C m it EIB / with EIB VMT-C D 90°C Option / O ption Langzeitbatterie / Longlife b atterie 10 Jahre
1,5 15 3
2,5 20 5
Wärmezähler
EIB-Schnittstelle integrierte EIB-Schnittstelle gem. EIB/KNX auslesbare Daten: Seriennummer, Energiewert, Stichtagswert, Volumen, Durchfluss, Wärmeleistung, Vor- und Rücklauftemperatur, Temperaturdifferenz
80 80 85523106 85563106 85533106 85543106 85573106 85623106 85663106 85633106 85643106 85673106 492010
Stand 10/2007 NORDWESTDEUTSCHE ZÄHLERREVISION Ing. Aug. Knemeyer GmbH & Co. KG
85523110 85563110 85533110 85543110 85573110 85623110 85663110 85633110 85643110 85673110
Technische Änderungen vorbehalten. www.nzr.de
+49 (0) 54 24 / 29 28 - 0
87
Wärmezähler WZ-HY heat meter WZ-HY Beschreibung / Description Rechenwerk / Counter Rechenwerk mit seperater Zulassung bis 180°C / Counter with separate approval up to 180°C
Temperaturdifferenz / Temperature difference: 2 … 130 K Zulassung für asymetrischen Einbau der Temperaturfühler / approval for asymmetric mountains of the temperature sensors
4-Bit Mikrocontroller / 4-bit micro-controller 7-stelliger Multifunktions-LCD / 7-digit multi function LCD
Berührungslose Display-Umschaltung / Non-contact display switching
Rechenwerkgehäuse 360° drehbar / Counter rotateable by 360°
umweltfreundlicher 3 V Lithium-Batterie / ecofriendly 3V lithium battery
Batterielebensdauer 5 Jahre plus 1 Jahr Gangreserve / battery service life 5 years plus 1 year power-reserve
Menüanzeigen / Menu displays Menü Menu
1
Beschreibung
Selbstkalibrierender Temperaturmesskreis / Dauer
Description
Time
Aktueller Verbrauchswert (Anzeige in kWh/MWh möglich) Seriennummer (6-stellig)
Kommunikation / Communication Fernauslesbar über / Readable from remote location via: M-Bus, D-Bus, S0
10
Volumenteil / Volume device Beliebige Einbaulagen / Any installation positions Volumenerfassung über elektronische Abtastung /
Serial number (6-digit)
3
Vorjahresverbrauchswert (Verbrauch am Stichtag)
10
Volume recording via electronical sensing (magnet-free)
Consumption value previous year (consumption on cut-off date)
optimale 2-Punkt-Lagerung aus Saphir/Hartmetall /
4
Displaytest / Display test
4
5
Aktuelles Datum / Current date
5
6
12 Monatsendwerte 12 month end value Vorlauftemperatur in °C
7
Je 6 125
Supply temperature in °C
8 9
Rücklauftemperatur in °C Return temperature in °C Akkumuliertes Volumen in m³
Display
Automatically calibrating temperature range
10
Current consumption value (display in kWh/MWh possible)
2
Display
125
optimal 2-point suspension made of sapphire/carbide metal
Temperaturbereich / Temperatur range:
0 – 120 °C
Temperaturfühler / Temperature sensor Typ / Type: Durchmesser / Diameter: Temperaturbereich / Temperature range: Temperaturdifferenz / Temperature difference: Kabellänge / Cable length:
Pt 500 5,2 mm 3 … 105 °C 2 … 130 K 1.5 m
10
Accumulated volume in m³
10
momentaner Durchfluss
125
current flow rate
11
momentane Leistung
125
Wärmezähler
current power
12
Fehleranzeige / Error display
5
13
Geeicht bis Monat/Jahr /
5
Zusätzliche Anzeigen / Additional signaling Modus Mode
SLEEP
calibrated till month/year
14
hohe Auflösung mit 3 Nachkommastellen Impulswertigkeit Rechenwerk [Liter]
5
impulse calculator [liter]
16
Impulswertigkeit Volumenteil [Liter]
5
ERROR Wird ein Checksummenfehler erkannt, oder der interne Fehlerzähler hat einen Überlauf, blinkt alle 8 Sekunden nebenstehende Darstellung. If a checksum error is found or the internal error counter has an overflow, ERROR will flash every 8 seconds.
impulse volume part [liter]
Funktionsanzeigen / Function displays Volumenimpuls
Symbol "Stern" zeigt eingehenden Volumenimpuls an. Symbol "star" shows incoming volume impulse.
Kommunikation
Symbol "Telefon" zeigt Aktualisierung der Netzwerkvariablen an. Symbol "phone" shows updating of network variables.
Gerätewechsel
Display Display
The display is switched off and SLEEP flashes every 8 seconds.
5
high precision with 3 decimal places
15
Beschreibung Description Das Display ist abgeschaltet und alle 8 Sekunden blinkt nebenstehende Darstellung.
PROG
Ist das Gerät in den Programmiermodus geschaltet, blinkt alle 8 Sekunden nebenstehende Darstellung. If the unit is in programming mode, PROG will flash every 8 seconds.
Zu Prüfzwecken kann die Daueranzeige des Wertes /!\ T * k durch eine Hardware-Steckbrücke aktiviert werden. The permanent signaling of the value /!\ T * k can be activated by a hardware jumper for testing purposes.
Symbol "Batterie" zeigt erschöpfte Batteriekapazität an. Symbol "battery" shows low battery capacity..
Stand 10/2007 88
NORDWESTDEUTSCHE ZÄHLERREVISION Ing. Aug. Knemeyer GmbH & Co. KG
Technische Änderungen vorbehalten. www.nzr.de
+49 (0) 54 24 / 29 28 - 0
m³/h mm m³/h
0,6 15 1,2
1,5 15 3
2,5 20 5
qp m³/h Trenngrenze / Transitional flow rate qt l/h Kleinster Durchfluss / Minimum flow rate q min l/h Anlauf / Starting flow rate l/h " Anschluss / Conection AG Zähler / Meter " AG Verschraubung / Screw connection L mm Baulänge / Length H mm Bauhöhe / Height E mm Breite Rechenwerk / Width Bestellinformationen / Order list WZ für trockene Fühler / for dry sensors mit Impuls / with impulse mit D-Bus/ with D-Bus mit M-Bus / with M-Bus mit EIB / with EIB mit LON / with LON WZ für nasse Fühler / for wet sensors mit Impuls / with impulse mit D-Bus/ with D-Bus mit M-Bus / with M-Bus mit EIB / with EIB mit LON / with LON
0,6 48 12 8 3/4 1/2 110
1,5 120 30 13 3/4 1/2 110 80 80
2,5 280 70 18 1 3/4 130
85323106 85363106 85333106 85343106 85373106 85353106 85423106 85463106 85433106 85413106 85473106 85453106
85323115 85363115 85333115 85343115 85373115 85353115 85423115 85463115 85433115 85443115 85473115 85453115
85323125 85363125 85333125 85343125 85373125 85353125 85423125 85463125 85433125 85443125 85473125 85443125
Dauerbelastung / Maximum working flow rate
qp DN qs
Stand 10/2007 NORDWESTDEUTSCHE ZÄHLERREVISION Ing. Aug. Knemeyer GmbH & Co. KG
Wärmezähler
Volumenteil / Volume device Nenndurchfluss / Flow rate Nennweite / Nominal diameter Maximale Belastung / Maximum flow rate
Technische Änderungen vorbehalten. www.nzr.de