Heat Meter / NZR APB KNX Heat Consumption Measuring Device

The following settings are available to set the parameters with ETS: The following is ... KG www.nzr.de +49 (0) 54 24 / 29 28 - 0 ... Displaytest / Display test. 4. 5.
1MB Größe 2 Downloads 476 Ansichten
KNX Heat Consumption Measuring Device Heat Meter / NZR

APB

Introduction The Arcus-EDS Heat Meter is a „Dialog WZ-CD / -HY“ Heat Consumption Counter (calibration optional) from the company NZR, with an integrated KNX Bus Interface for remote reading and monitoring. The electronic counter is operated by a lithium battery with a 5-year lifespan and 1-year additional reserve. The KNX bus interface is built into the counter and is connected non-reactively with the external terminal block. The meter with the integrated bus interface is authorized by the Physikalisch Technischen Bundesanstalt (PTB) (German Federal Institute of Physics and Metrology).

Pic. 1 Heat Meter with KNX Connector

Pic. 2 Open KNX Connector Housing

KNX – Interface The following items are available for remote reading with the KNX/EIB System: Nr. 0 1 2 3 4 5 6 7 8

Current Output in kWh/h Accumulated Volume in m3 Flow Temperature in °C Return Temperature in °C Current Flow m3/h Current Consumption Saved Value for Due Date Serial Number Error Message

Current Output Accumulated Volume Flow Temperature Return Temperature Current Flow Current Consumption Saved Value for Due Date Serial Number Error Message

Data Point Type DPT14.056 = Output DPT14.076 = Volume DPT9.001 = Degrees Celsius DPT9.001 = Degrees Celsius DPT14.077 = Volume Flow DPT14.056 = Output DPT14.056 = Output DPT16.000 = String DPT7.001=2 Unsigned Byte

Data Type Measurement 4 Byte Integrator 4 Byte Measurement 2 Byte Measurement 2 Byte Measurement 4 Byte Measurement 4 Byte Integrator 4 Byte Identification 14 Byte System Status 2 Byte

in kWh/h, the current output in the system. in m3, the total amount of flow through water. in °C, the temperature of the water in the system. in °C, the temperature of the water returning to the system. m3/h, the current amount of flow through water. in kWh, the accumulated warmth output. in kWh, the accumulated warmth output for a particular date ( internal value in the meter ). String, for positive identification of the meter. Error Report with Error Code from the manufacturer.

None of the items can be altered from the bus.

Arcus-EDS GmbH, Rigaer Str. 88, 10247 Berlin, Tel.: 0049/30/25933914, Fax: 0049/30/25933915 [email protected] www.arcus-eds.de

610

e11

KNX Heat Consumption Measuring Device Heat Meter / NZR

APB

Parameter: The following settings are available to set the parameters with ETS:

The following is available for all items except Serial Number and Error Number: Periodic Transmission (2min) Transmission - Change No Transmission

The current measurement is transmitted every 2 minutes to the bus. The current measurement is transmitted to the bus only when a change occurs (minimum interval 2 min). The current measurement is not transmitted automatically (Measurements are read manually).

Installation The heat meter must only be installed and put into operation by an authorized specialist. In addition, knowledge of Engineering Tool Software (ETS) is required. Set-up is carried out with ETS Version 2 or higher. You will find the heat meter in ETS under manufacturer: Arcus-eds, Product Family: Meter, Product Type: heat meter. The EIB programming button and programming LED are located on the attached housing. (see above). Technical data for the heat meter can be found in the data sheet of the manufacturer NZR: Technical Documentation Heat Meter Dialog WZ-HY db-wz-cd.pdf / db-wz-hy.pdf (see attached)

Program de-activate and reset sensor: If there is an error in programming and the counter no longer reacts, you can delete the project by pressing the program button. Press the program button down while connecting the EIB bus clamp and wait for the program LED to light up. This takes from 5-10 seconds.

Arcus-EDS GmbH, Rigaer Str. 88, 10247 Berlin, Tel.: 0049/30/25933914, Fax: 0049/30/25933915 [email protected] www.arcus-eds.de

610

e11

KNX Heat Consumption Measuring Device Heat Meter / NZR

APB

Imprint: Publisher: Arcus-EDS GmbH, Rigaer Str. 88, 10247 Berlin Responsible for Content: Hjalmar Hevers, Reinhard Pegelow Reprints, including partial reprints, can be made only with expressed permission from Arcus-EDS GmbH. This information is the best to our knowledge and is without guarantee. We reserve the right to make any technical and price changes at any time. Liability: Selection and determining the appropriateness of the devices for a designated purpose is the customer’s full responsibility. We offer no liability or guarantee for this. The data in the catalogue and data sheets is a result of experienced measurements and does not embody a guarantee of particular features. Arcus excludes responsibility for damage done on the part of the customer due to improper operation/projecting or malfunctions. On the contrary, the operator/projector must ensure that improper operation, and projection and malfunctions do not lead to any further damage. Safety Guidelines: Attention! Installing and assembling electrical devices must only be done by an electronics specialist. The customer should be aware of and adhere to the safety guidelines of VDE, TÜV and the appropriate energy provider. Our guarantee does not include defects and damage caused by improper use or non-compliance of operating instructions. Warranty: We provide a warranty as required by law. Please contact us in case of malfunction and send the device with a full description of the fault to the address below Manufacturer:

Registered Trademarks: The CE Trademark is an unofficial market trademark used exclusively by authorities and provides no warranty of properties. Registered Trademark of Konnex Association

Arcus-EDS GmbH, Rigaer Str. 88, 10247 Berlin, Tel.: 0049/30/25933914, Fax: 0049/30/25933915 [email protected] www.arcus-eds.de

610

e11

Wärmezähler WZ-CD heat meter WZ-CD Beschreibung / Description Rechenwerk / Counter ƒ Rechenwerk mit seperater Zulassung bis 180°C / Counter with separate approval up to 180°C

ƒ Temperaturdifferenz / Temperature difference: 2 … 130 K ƒ Zulassung für asymetrischen Einbau der Temperaturfühler / approval for asymmetric mountains of the temperature sensors

ƒ 4-Bit Mikrocontroller / 4-bit micro-controller ƒ 7-stelliger Multifunktions-LCD / 7-digit multi function LCD

ƒ Berührungslose Display-Umschaltung / Non-contact display switching

ƒ Rechenwerkgehäuse 355° drehbar / Counter rotateable by 355°

ƒ umweltfreundlicher 3 V Lithium-Batterie / ecofriendly 3V lithium battery

ƒ Batterielebensdauer 5 Jahre plus 1 Jahr Gangreserve / battery service life 5 years plus 1 year power-reserve

ƒ Selbstkalibrierender Temperaturmesskreis / Automatically calibrating temperature range

Menüanzeigen / Menu displays Menü Menu

1

Beschreibung

Dauer

Description

Time

10

Aktueller Verbrauchswert (Anzeige in kWh/MWh möglich) Current consumption value (display in kWh/MWh possible)

2

Seriennummer (6-stellig)

3

Vorjahresverbrauchswert (Verbrauch am Stichtag)

10

Serial number (6-digit)

10

Displaytest / Display test

4

5

Aktuelles Datum / Current date

5

6

12 Monatsendwerte 12 month end value Vorlauftemperatur in °C

Je 6 125

Supply temperature in °C

9

Rücklauftemperatur in °C Return temperature in °C Akkumuliertes Volumen in m³

Kommunikation / Communication ƒ Fernauslesbar über / Readable from remote location via: EIB, M-Bus, D-Bus, S0 Volumenteil / Volume device ƒ Beliebige Einbaulagen / Any installation positions ƒ Überkopfeinbau / Overarm installation ƒ Volumenerfassung über elektronische Abtastung (magnetfrei) / Volume recording via electronical sensing (magnet-free) optimal 2-point suspension made of sapphire/carbide metal

4

8

Display

ƒ optimale 2-Punkt-Lagerung aus Saphir/Hartmetall /

Consumption value previous year (consumption on cut-off date)

7

Display

125

ƒ Temperaturbereich / Temperatur range: ƒ Opional Temp.-Bereich / optional temp-range

15 - 90 °C 15 - 120 °C

Temperaturfühler / Temperature sensor ƒ Typ / Type: ƒ Durchmesser / Diameter: ƒ Temperaturbereich / Temperature range: ƒ Temperaturdifferenz / Temperature difference: ƒ Kabellänge / Cable length:

Pt 500 5,2 mm 3 … 105 °C 2 … 130 K 1.5 m

10

Accumulated volume in m³

10

momentaner Durchfluss

125

current flow rate

11

momentane Leistung

125

Wärmezähler

current power

12 13

Fehleranzeige / Error display

5

Geeicht bis Monat/Jahr /

5

calibrated till month/year

14

hohe Auflösung mit 3 Nachkommastellen

5

high precision with 3 decimal places

15

Impulswertigkeit Rechenwerk [Liter]

5

impulse calculator [liter]

16

Impulswertigkeit Volumenteil [Liter]

5

impulse volume part [liter]

Funktionsanzeigen / Function displays Volumenimpuls

Symbol "Stern" zeigt eingehenden Volumenimpuls an. Symbol "star" shows incoming volume impulse.

Kommunikation

Symbol "Telefon" zeigt Aktualisierung der Netzwerkvariablen an. Symbol "phone" shows updating of network variables.

Gerätewechsel

Symbol "Batterie" zeigt erschöpfte Batteriekapazität an. Symbol "battery" shows low battery capacity..

Stand 10/2007 86

NORDWESTDEUTSCHE ZÄHLERREVISION Ing. Aug. Knemeyer GmbH & Co. KG

Technische Änderungen vorbehalten. www.nzr.de

+49 (0) 54 24 / 29 28 - 0

Wärmezähler WZ-CD heat meter WZ-CD Kommunikationsoptionen

Communication options

Impulsausgang ƒ SO (open Kollektor) oder potentialfreier Kontakt ƒ Impulswertigkeit: - 1 kWh/Imp bei kWh-Anzeige - 10 kWh/Imp bei MWh-Anzeige

Impulse output ƒ SO (open collector) or potential-free contact ƒ Impulse value: - 1 kWh/Imp with kWh display - 10 kWh/Imp with MWh display D-Bus interface ƒ economical dialogue bus (twin-wire technology) ƒ readable data: Serial number, energy value, cut-off date value, volume, flow rate, heating power, supply and return temperature, temperature difference

D-Bus-Schnittstelle ƒ kostengünstiger Dialog-Bus (2-Drahttechnik) ƒ auslesbare Daten: Seriennummer, Energiewert, Stichtagswert, Volumen, Durchfluss, Wärmeleistung, Vor- und Rücklauftemperatur, Temperaturdifferenz

M-Bus interface ƒ integrated M-Bus interface in accordance with. EN 1434-3 ƒ readable data: Serial number, energy value, cut-off date value, volume, flow rate, heating power, supply and return temperature, temperature difference

M-Bus-Schnittstelle ƒ integrierte M-Bus-Schnittstelle gem. EN 1434-3 ƒ auslesbare Daten: Seriennummer, Energiewert, Stichtagswert, Volumen, Durchfluss, Wärmeleistung, Vor- und Rücklauftemperatur, Temperaturdifferenz

EIB interface ƒ integrated EIB interface in accordance with. EIB/KNX ƒ readable data: Serial number, energy value, cut-off date value, volume, flow rate, heating power, supply and return temperature, temperature difference

Volum enteil / Vo l u m e d evi ce N enndurchflus s / F low rate N ennw eite / Nominal diameter Maxim ale Belas tung / Max imum flow rate D auerbelas tung / Max imum work ing flow rate Trenngrenze / T rans itional flow rate Kleins ter D urchflus s / Minimum flow rate

qp DN qs

m ³/h mm m ³/h

0,6 15 1,2

1,0 15 2

qp

m ³/h

0,6

1,0

1,5

2,5

qt q min

l/h l/h l/h " " mm mm mm

48 12 8 3/4 1/2 110

80 20 11 3/4 1/2 110

120 30 13 3/4 1/2 110

280 70 18 1 3/4 130

85523115 85563115 85533115 85543115 85573115 85623115 85663115 85633115 85643115 85673115

85523125 85563125 85533125 85543125 85573125 85623125 85663125 85633125 85643125 85673125

Anlauf / Starting flow rate Ans chlus s / Conec tion AG Zähler / Meter AG Vers chraubung / Sc rew c onnec tio Ba ulänge / Length L Ba uhöhe / Height H Breite R e chenw erk / W idth E Be stellinform ationen / O r d er l i st WZ für trockene Fühler / for dry s ens ors VMT-C D 90°C m it Im puls / with impuls e VMT-C D 90°C m it D -Bus / with D-Bus VMT-C D 90°C m it M-Bus / with M-Bus VMT-C D 90°C m it EIB / with EIB VMT-C D 90°C WZ für nas s e Fühler / for wet s ens ors VMT-C D 90°C m it Im puls / with impuls e VMT-C D 90°C m it D -Bus / with D-Bus VMT-C D 90°C m it M-Bus / with M-Bus VMT-C D 90°C m it EIB / with EIB VMT-C D 90°C Option / O ption Langzeitbatterie / Longlife b atterie 10 Jahre

1,5 15 3

2,5 20 5

Wärmezähler

EIB-Schnittstelle ƒ integrierte EIB-Schnittstelle gem. EIB/KNX ƒ auslesbare Daten: Seriennummer, Energiewert, Stichtagswert, Volumen, Durchfluss, Wärmeleistung, Vor- und Rücklauftemperatur, Temperaturdifferenz

80 80 85523106 85563106 85533106 85543106 85573106 85623106 85663106 85633106 85643106 85673106 492010

Stand 10/2007 NORDWESTDEUTSCHE ZÄHLERREVISION Ing. Aug. Knemeyer GmbH & Co. KG

85523110 85563110 85533110 85543110 85573110 85623110 85663110 85633110 85643110 85673110

Technische Änderungen vorbehalten. www.nzr.de

+49 (0) 54 24 / 29 28 - 0

87

Wärmezähler WZ-HY heat meter WZ-HY Beschreibung / Description Rechenwerk / Counter ƒ Rechenwerk mit seperater Zulassung bis 180°C / Counter with separate approval up to 180°C

ƒ Temperaturdifferenz / Temperature difference: 2 … 130 K ƒ Zulassung für asymetrischen Einbau der Temperaturfühler / approval for asymmetric mountains of the temperature sensors

ƒ 4-Bit Mikrocontroller / 4-bit micro-controller ƒ 7-stelliger Multifunktions-LCD / 7-digit multi function LCD

ƒ Berührungslose Display-Umschaltung / Non-contact display switching

ƒ Rechenwerkgehäuse 360° drehbar / Counter rotateable by 360°

ƒ umweltfreundlicher 3 V Lithium-Batterie / ecofriendly 3V lithium battery

ƒ Batterielebensdauer 5 Jahre plus 1 Jahr Gangreserve / battery service life 5 years plus 1 year power-reserve

Menüanzeigen / Menu displays Menü Menu

1

Beschreibung

ƒ Selbstkalibrierender Temperaturmesskreis / Dauer

Description

Time

Aktueller Verbrauchswert (Anzeige in kWh/MWh möglich) Seriennummer (6-stellig)

Kommunikation / Communication ƒ Fernauslesbar über / Readable from remote location via: M-Bus, D-Bus, S0

10

Volumenteil / Volume device ƒ Beliebige Einbaulagen / Any installation positions ƒ Volumenerfassung über elektronische Abtastung /

Serial number (6-digit)

3

Vorjahresverbrauchswert (Verbrauch am Stichtag)

10

Volume recording via electronical sensing (magnet-free)

Consumption value previous year (consumption on cut-off date)

ƒ optimale 2-Punkt-Lagerung aus Saphir/Hartmetall /

4

Displaytest / Display test

4

5

Aktuelles Datum / Current date

5

6

12 Monatsendwerte 12 month end value Vorlauftemperatur in °C

7

Je 6 125

Supply temperature in °C

8 9

Rücklauftemperatur in °C Return temperature in °C Akkumuliertes Volumen in m³

Display

Automatically calibrating temperature range

10

Current consumption value (display in kWh/MWh possible)

2

Display

125

optimal 2-point suspension made of sapphire/carbide metal

ƒ Temperaturbereich / Temperatur range:

0 – 120 °C

Temperaturfühler / Temperature sensor ƒ Typ / Type: ƒ Durchmesser / Diameter: ƒ Temperaturbereich / Temperature range: ƒ Temperaturdifferenz / Temperature difference: ƒ Kabellänge / Cable length:

Pt 500 5,2 mm 3 … 105 °C 2 … 130 K 1.5 m

10

Accumulated volume in m³

10

momentaner Durchfluss

125

current flow rate

11

momentane Leistung

125

Wärmezähler

current power

12

Fehleranzeige / Error display

5

13

Geeicht bis Monat/Jahr /

5

Zusätzliche Anzeigen / Additional signaling Modus Mode

SLEEP

calibrated till month/year

14

hohe Auflösung mit 3 Nachkommastellen Impulswertigkeit Rechenwerk [Liter]

5

impulse calculator [liter]

16

Impulswertigkeit Volumenteil [Liter]

5

ERROR Wird ein Checksummenfehler erkannt, oder der interne Fehlerzähler hat einen Überlauf, blinkt alle 8 Sekunden nebenstehende Darstellung. If a checksum error is found or the internal error counter has an overflow, ERROR will flash every 8 seconds.

impulse volume part [liter]

Funktionsanzeigen / Function displays Volumenimpuls

Symbol "Stern" zeigt eingehenden Volumenimpuls an. Symbol "star" shows incoming volume impulse.

Kommunikation

Symbol "Telefon" zeigt Aktualisierung der Netzwerkvariablen an. Symbol "phone" shows updating of network variables.

Gerätewechsel

Display Display

The display is switched off and SLEEP flashes every 8 seconds.

5

high precision with 3 decimal places

15

Beschreibung Description Das Display ist abgeschaltet und alle 8 Sekunden blinkt nebenstehende Darstellung.

PROG

Ist das Gerät in den Programmiermodus geschaltet, blinkt alle 8 Sekunden nebenstehende Darstellung. If the unit is in programming mode, PROG will flash every 8 seconds.

Zu Prüfzwecken kann die Daueranzeige des Wertes /!\ T * k durch eine Hardware-Steckbrücke aktiviert werden. The permanent signaling of the value /!\ T * k can be activated by a hardware jumper for testing purposes.

Symbol "Batterie" zeigt erschöpfte Batteriekapazität an. Symbol "battery" shows low battery capacity..

Stand 10/2007 88

NORDWESTDEUTSCHE ZÄHLERREVISION Ing. Aug. Knemeyer GmbH & Co. KG

Technische Änderungen vorbehalten. www.nzr.de

+49 (0) 54 24 / 29 28 - 0

m³/h mm m³/h

0,6 15 1,2

1,5 15 3

2,5 20 5

qp m³/h Trenngrenze / Transitional flow rate qt l/h Kleinster Durchfluss / Minimum flow rate q min l/h Anlauf / Starting flow rate l/h " Anschluss / Conection AG Zähler / Meter " AG Verschraubung / Screw connection L mm Baulänge / Length H mm Bauhöhe / Height E mm Breite Rechenwerk / Width Bestellinformationen / Order list WZ für trockene Fühler / for dry sensors mit Impuls / with impulse mit D-Bus/ with D-Bus mit M-Bus / with M-Bus mit EIB / with EIB mit LON / with LON WZ für nasse Fühler / for wet sensors mit Impuls / with impulse mit D-Bus/ with D-Bus mit M-Bus / with M-Bus mit EIB / with EIB mit LON / with LON

0,6 48 12 8 3/4 1/2 110

1,5 120 30 13 3/4 1/2 110 80 80

2,5 280 70 18 1 3/4 130

85323106 85363106 85333106 85343106 85373106 85353106 85423106 85463106 85433106 85413106 85473106 85453106

85323115 85363115 85333115 85343115 85373115 85353115 85423115 85463115 85433115 85443115 85473115 85453115

85323125 85363125 85333125 85343125 85373125 85353125 85423125 85463125 85433125 85443125 85473125 85443125

Dauerbelastung / Maximum working flow rate

qp DN qs

Stand 10/2007 NORDWESTDEUTSCHE ZÄHLERREVISION Ing. Aug. Knemeyer GmbH & Co. KG

Wärmezähler

Volumenteil / Volume device Nenndurchfluss / Flow rate Nennweite / Nominal diameter Maximale Belastung / Maximum flow rate

Technische Änderungen vorbehalten. www.nzr.de

+49 (0) 54 24 / 29 28 - 0

89