VDE-AR-N 4105:2011 F.3 F.3 Requirements for the test reports for power generation units Extract from test report for unit certificate “Determination of electrical properties”
No. 3AXD10000050547
Type of system: PVS300-TL-XX00W-2 ABB Oy System manufacturer Hiomotie 13 FI‐00380 Helsinki Finland
Manufacturer’s data Type of system Active power (nominal) 3,3…8,0 kW Rated voltage 230 V
Measuring period: from 2011-10-31 to 2011-12-16 Active power 3,3…8,0 kW Reactive power reference Active power P/Pn [%] 10 Max possible cosϕ underexcited 0.92 Max possible cosϕ overexited 0.87
20 0.91 0.89
30 0.91 0.89
40 0.91 0.89
50 0.91 0.89
60 0.91 0.89
70 0.91 0.89
80 0.91 0.89
90 0.91 0.89
100 0.91 0.89
0.960 un
0.940 un
0.920 un
0.900 un
Compliance of required displacement factor cos ϕ Default in system control Measured value at PGU terminals
0.900 ov
0.920 ov
0.940 ov
0.960 ov
0.980 ov
1.0 0.980 un
0.892 0.913 0.933 0.955 0.976 1.0 0.984
0.965 0.964 0.925 0.906
Reactive power transfer function – Standard -cos ϕ ‐(P) ‐characteristic Active poweer P/Pn[%] cos ϕ
10 ‐
20 30 0.948 0.965
Switching actions Making operation without default Worst case at switch over of generator sections Making operation at reference conditions Breaking operation at nominal power Worst-case value of all switching operations
40 50 60 70 80 90 100 0.982 0.998 0.978 0.957 0.935 0.915 0.894
ki: 1.0 ki: ki. 1.0 ki: 1.0 Ki max: 1.0
Flicker Angle of network impedanceψk Coefficient of system flicker Cψ
DMS code: 3AXD10000050457
32° 0,124
VDE-AR-N 4105:2011 F.3 Harmonics - Active power
DMS code: 3AXD10000050457
VDE-AR-N 4105:2011 F.3 Subharmonics – Active power
DMS code: 3AXD10000050457
VDE-AR-N 4105:2011 F.3 Higher Frequencies – Active power
DMS code: 3AXD10000050457