Technical Catalogue, Version June 2014
Back-up and Selectivity tables S800, SMISSLINE with ABB Products
Content
Back-up protection at 230/400 V
Selectivity at 400/415V
Tmax/Fuse -S800B
5
-S400/S450
5
XT -S800B
5
Selectivity at 400/415V
-S400/S450
5
Tmax -DS400
Tmax/Fuse -DS401
6
XT -DS401
6
S800S
-S60, -S200
7
-S280, -S400
8
-SN201 -S60, -S200
10
-S280, -S400
11
S800C
-S60, S200
-S280, -S400
13 14–15 16
S800B -S200
17
-S400
18
S800B -SN201
19
S800U
20
-S200
21
22
-S280, -S400
68–69
12
-SN201
-S60, -S200
64–67
9
S800N
-SN201
Tmax -S400
Back-up protection at 240 V Tmax/Fuse -S800U
23
Back-up protection at 415 V Tmax -S800
24
XT -S800
24
Back-up protection at 254/440 V S800S, -N
-S400, -S450M
25
Selectivity at 230/400 V Fuse -S400
26
S400 -S400 27–28 S800S -S200
29–34
S800S -S400
35–37
Selectivity at 230/400 V S800N -S200
38–43
-S400
44–46
Selectivity at 400/415 V Tmax -S800S
47–49
-S800N 50–51
Selectivity at 254/440 V S800S -S400M
52–53
S800N -S400M
54–55
Miniature circuit breaker S400M Selectivity to Sace Tmax T1, T2
56–62
Selectivity at 690 V Fuse
-S800 63 Back-up and Selectivity tables | S800, SMISSLINE with ABB Products 3
Back-up and selectivity dates S400/S450, FS401, FS403 and S800 S800N – S400E @ 230/400 V
Supply side
Upstream Char. I cu [kA]
Downstream
Load side
S400E
B
6
In [A] 6 10 13 16 20 25 32 40 36 63
25 36 36 36 36
32 36 36 36 36 36
40 36 36 36 36 36 36
S800N B, C, D 36 50 63 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36
80 36 36 36 36 36 36 36 36 36
100 125 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36
Example 1: With a S800Nominal current 50 A is a Back-up protection till a nominal current of 25 A to a S400 given. The Back-up protection ist till 36 kA. Example 2: There is no Back-up protection between supply side and the load side given. Back-up protection The tables given provide the value (in kA, referring to the breaking capacity) for which the back-up protection among the combination of selected circuit breakers is verified. The tables cover the possible combinations between S800 and those between the above mentioned circuit breakers and the ABB series of modular circuit breakers S400. The values indicated in the tables refer to the voltage: – Vn of 230/400 VAC Upstream Char. Downstream
I cu [kA]
50
S400M S450M
C
25
15
In [A] 0.5 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63
25 T T T T 0.7 0.6 0.5 0.4 0.4 0.4
32 T T T T 2 1.2 0.9 0.5 0.5 0.5 0.5
40 T T T T 4 2 1.1 0.8 0.8 0.8 0.8 0.7 0.7
S800S D 50 50 63 T T T T T T T T T T 4 7 1.8 2.5 1 1.3 1 1.3 1 1.3 1 1.3 1 1.2 1 1.2 0.9 1 1
80 100 125 T T T T T T T T T T T T T T T T T T 9 T T 2.5 3.5 6.7 2.5 3.5 6.7 2.3 3 5.1 2.3 3 5.1 2.1 2.7 4.3 2.1 2.7 4.3 1.7 2.2 3.4 1.7 2.2 3.4 1.4 1.7 2.1 1.6 2.1
Example 1: In this combination is a selectivity switch off till 5.1 kA given. Example 2: There is no selectivity. Selective protection The tables given provide the value (in kA, referring to the breaking capacity) for which the selective protection is verified among the combination of selected circuit breakers. The tables cover the possible combinations between S800 and the ABB series of modular circuit breakers. The values in the table represent the maximum value obtainable of discrimination between supply side circuit breaker and load side circuit breaker referring to the voltage: – Vn of 230/400 VAC
Consulting the back-up table This table provides the value (in kA) for which the back-up protection is ensured between a given combination of circuit b reakers. The table covers possible combinations between the S800, Tmax, SMISSLINE MCBs, S60 and S200. Tmax and between SMISSLINE miniature circuit breakers S400/S450. a) If the short-circuit current at the point of installation of the circuit breaker is not greater than the nominal breaking capacity of the MCB, an upstream fuse is not needed. If a fuse is fitted upstream for installation reasons, any nominal current may be selected for the fuse. b) If the short-circuit current at the point of installation of the circuit breaker is greater than its nominal breaking capacity, the nominal currents of the upstream fuses must not exceed the values specified in the table (back-up protection of the circuit breaker). 4 S800, SMISSLINE with ABB Products | Back-up and Selectivity tables
Back-up protection Fuses NH/Tmax – S400/S450, S800 Upstream: Fuse NH..gL/gG Upstream I cu [kA]
Downstream S400M/S450M FS401M/FS451M FS403M/FS453M S400E/S450E FS401E/FS451E FS403E/FS453E
NH gL/gG
In [A]
25
40
63
Icn [kA] 10
all types
100 100 100 100
80
50
30
20
Icn [kA] 6
all types
100 100
25
15
10
–
70
80
40
100 125 160 200
Tmax – S800B @ 230/400 V
Downstream S800B
Char.
ln [A]
B, C
32...100
D, K
125*
Upstream
T1
T1
T2
T4
Version
B
C
N
S
H
L
L
V
lcu [kA]
16
25
36
50
70
85
120
200
16
T1
T2
T3
T4
T2
T3
T4
T2
T4
T4
25
36
36
36
36
50
50
50
70
70
85
120
200
25
36
36
36
36
50
50
50
70
70
85
120
200
T2
T4
T4
Sace Tmax – S400 @ 230/400 V T1
T1
T1
T2
T3
T4
T2
T3
T4
T2
T4
Version
B
C
N
N
N
N
S
S
S
H
H
lcu [kA]
16
25
36
36
36
36
50
50
50
70
70
85
120
200
36
36
40
40
40
30
40
40
40
6
16
25
30
36
16
16
16
16
16
16
16
40
40
50
40
50
40
40
10
16
25
30
36
25
40
50
40
50
40
40
40
40
50
40
50
40
40
10
16
25
30
36
25
40
50
40
50
40
40
Upstream Version ln [A]
Downstream S400E/S450E FS401E/FS451E FS403E/FS453E
6…10 B, C 13…63
S400M/S450M FS401M/FS451M C, K FS403M/FS453M
0.5…10
S400M/S450M FS401M/FS451M B, D FS403M/FS453M
6…10
13…63
13…63
16
16
36
36
25
36
36
36
25
36
40
40
36
L
V
Sace XT - DS400 @230/400V Supply side 415 V AC
XT2
XT2
XT2
XT2
Version
N
S
H
V
Load side 240 V AC
ln [A]
lcu [kA]
36
50
70
150
DS401M DS402M
≤ 40
10
36
40
40
40
Supply side 415 V AC
XT1
XT1
XT1/XT3/XT4
XT1/XT3/XT4
XT1/XT4
XT4
XT4
Version
B
C
N
S
H
L
V
Load side 240 V AC
ln [A]
lcu [kA]
18
25
36
50
70
120
150
DS401M
≤ 20
10
18
20
20
20
20
20
20
DS402M
25 to 40
10
10
10
10
10
10
10
10
XT – S800B @ 230/400 V Upstream Downstream S800B
Char.
ln [A]
B, C
32...100
D, K
125*
XT1
XT1
Version
B
C
lcu [kA]
18
25
120
120
18
25
36
36
36
36
50
50
50
50
70
70
70
120
120
150
150
18
25
36
36
36
36
50
50
50
50
70
70
70
120
120
150
150
XT3
XT4
XT1
XT2
XT3
XT4
XT1
XT2
XT4
16
XT1
XT2
XT3
XT4
XT1
XT2
N
XT3
XT4
XT1
S
36
XT2
XT4
XT2
H
50
XT4
XT2
L
70
XT4 V
150
Sace XT – S400 @ 230/400 V XT1
Upstream Version Downstream FS400E S400E S450E FS400M S400M S450M FS400M S400M S450M
ln [A] B, C C, K B, D
6…10 13…63 0.5…10 13…63 6…10 13…63
XT2
Version
B
C
N
lcu [kA]
18
25
36
S 50 36
6
18
25
30
36
10
18
25
30
36
10
18
25
30
36
16
36
30
36
36
30
50
36
30
50
16
40
30
40
30
40
30
40
36 25
XT4
XT2
XT4
L
V
70
120
150
40
36 25
XT2
H
25
40
70
40 25
40
60
40
85 40
70 60
40
60 60
40
85 40
85 40
40
60
40
85 40
60
40
Selectivity limits are specified in kA
Back-up and Selectivity tables | S800, SMISSLINE with ABB Products 5
Back-up protection Fuses – MCB – DS401, DS451 MCB -MCB @ 240 V Supply side
25gG
40gG
50gG
63gG
80gG
100gG
Char. Icu [kA]
Load side
In [A]
DS401 DS451
B, C
10
2…40
35
25
20
15
10
10
DS401M/ DS402M DS451M
B, C
10
2…40
35
25
20
15
10
10
MCCB @ 415 V – MCB/RCBO @ 240 V Supply side 1 Char. Load side
Version Icu [kA]
T1 C 25
T1
16
16
16
T2 N 36
T3
T2
T3 S 50
T2 H 70
T2 L 85
25
25
16
16
25
25
16
16
In [A] 2…25
DS401 DS451
B, C, D, K
10
DS401M/ DS402M DS451M
B, C
10
1
T1 B 16
25
32, 40
16
2…25 16
16
16 16
25 16
32, 40
25 16
25 16
16
16 16
Supply side circuit-breaker 4P (load side circuit branched between one phase and the neutral
6 S800, SMISSLINE with ABB Products | Back-up and Selectivity tables
Back-up protection S800S – S60, -S200, -S200M, -S200P S800S – S60 @ 230/400 V
S800S – S200M @ 230/400 V
Upstream Char. Icu [kA]
Downstream
S60
C
In [A] 2 4 6 8 10 13 16 20 25 32 40 50 63
6
25 50 50 50 50 50 50 50
32 50 50 50 50 50 50 50 50
40 50 50 50 50 50 50 50 50 50
S800S B, C, D, K 50 50 63 25 18 25 18 25 18 25 18 25 18 25 18 25 18 25 18 25 18 25 18 18
Upstream Char. 80 15 15 15 15 15 15 15 15 15 15 15 15
100 125 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
Icu [kA]
Downstream
S200M
B
15
Upstream Icu [kA]
Downstream
S200
B
In [A] 6 10 13 16 20 25 32 40 50 63
10
25 50 50 50 50
32 50 50 50 50 50
40 50 50 50 50 50 50
Upstream Char. Icu [kA]
Downstream
S200
C
10
In [A] 0.5…6 8 10 13 16 20 25 32 40 50 63
25 50 50 50 50 50
32 50 50 50 50 50 50
40 50 50 50 50 50 50 50
S800S B, C, D, K 50 50 63 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
S800S B, C, D, K 50 50 63 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
100 125 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
C
15
In [A] 0.5…16 20 25 32 40 50 63
25 50
32 50 50
40 50 50 50
S800S B, C, D, K 50 50 63 50 50 50 50 50 50 50 50 50
80 50 50 50 50 50 50
100 125 50 50 50 50 50 50 50 50 50 50 50 50 50 50
80 50 50 50 50 50 50
100 125 50 50 50 50 50 50 50 50 50 50 50 50 50 50
80 50 50 50 50 50 50
100 125 50 50 50 50 50 50 50 50 50 50 50 50 50 50
80 50 50 50 50 50 50
100 125 50 50 50 50 50 50 50 50 50 50 50 50 50 50
S800S – S200P @ 230/400 V Upstream Char. Icu [kA]
Downstream
25 B 15
100 125 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
40 50 50 50
Icu [kA]
Downstream
S200P
80 50 50 50 50 50 50 50 50 50 50
32 50 50
Upstream
S200M
80 50 50 50 50 50 50 50 50 50
25 50
Char.
S800S – S200 @ 230/400 V Char.
In [A] 6…16 20 25 32 40 50 63
S800S B, C, D, K 50 50 63 50 50 50 50 50 50 50 50 50
In [A] 6…16 20 25 32 40 50 63
25 50
32 50 50
40 50 50 50
Upstream Char. Icu [kA]
Downstream
25 S200P
C 15
In [A] 0.5…16 20 25 32 40 50 63
25 50
32 50 50
40 50 50 50
S800S B, C, D, K 50 50 63 50 50 50 50 50 50 50 50 50
S800S B, C, D, K 50 50 63 50 50 50 50 50 50 50 50 50
S800S – S200L @ 230/400 V Upstream Char. Icu [kA]
Downstream
S200L
C
6
In [A] 6...8 10 13 16 20 25 32 40
25 50 50 50 50
32 50 50 50 50 50
40 50 50 50 50 50 50
S800S B, C, D, K 50 50 63 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
80 50 50 50 50 50 50 50 50
100 125 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
Backup limit values indicated in kA
Back-up and Selectivity tables | S800, SMISSLINE with ABB Products 7
Back-up protection S800S – S280, -S400E, -S400M S800S – S400E @ 230/400 V
S800S – S280 @ 230/400 V Upstream Char. Icu [kA]
Downstream
10
S280
B
25
15 10
In [A] 6 10 13 16 20 25 32 40 50 63
25 50 50 50 50
32 50 50 50 50 50
40 50 50 50 50 50 50
Upstream Char. Icu [kA]
Downstream
10
S280
C
25
15 10
In [A] 3 4 6 8 10 13 16 20 25 32 40 50 63
25 50 50 50 50 50 50 50
32 50 50 50 50 50 50 50 50
40 50 50 50 50 50 50 50 50 50
Upstream Char. Icu [kA]
Downstream
10
S280
K, Z
25
15 10
In [A] 3 4 6 8 10 13 16 20 25 32 40 50 63
25 50 50 50 50 50 50 50
32 50 50 50 50 50 50 50 50
40 50 50 50 50 50 50 50 50 50
S800S B, C, D, K 50 50 63 50 50 25 20 25 20 25 20 25 20 25 20 25 20 20
S800S B, C, D, K 50 50 63 50 50 50 50 50 50 25 20 25 20 25 20 25 20 25 20 25 20 25 20 20
S800S B, C, D, K 50 50 63 50 50 50 50 50 50 25 20 25 20 25 20 25 20 25 20 25 20 25 20 20
Upstream Char. 80 50 16 16 16 16 16 16 16 16
100 125 50 50 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
Icu [kA]
Downstream
Icn [kA] 6
S400E
B
In [A] 6 10 13 16 20 25 32 40 50 63
25 50 50 50 50
32 50 50 50 50 50
40 50 50 50 50 50 50
Upstream Char. 80 50 50 50 16 16 16 16 16 16 16 16 16
100 125 50 50 50 50 50 50 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
Icu [kA]
Downstream
Icn [kA]
6 S400E
C
In [A] 0.5...6 8 10 13 16 20 25 32 40 50 63
25 50 50 50 50 50
32 50 50 50 50 50 50
40 50 50 50 50 50 50 50
S800S B, C, D, K 50 50 63 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
S800S B, C, D, K 50 50 63 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
80 50 50 50 50 50 50 50 50 50
100 125 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
80 50 50 50 50 50 50 50 50 50 50
100 125 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
80 50 50 50 50 50 50
100 125 50 50 50 50 50 50 50 50 50 50 50 50 50 50
80 50 50 50 50 50 50
100 125 50 50 50 50 50 50 50 50 50 50 50 50 50 50
S800S – S400M @ 230/400 V Upstream 80 50 50 50 16 16 16 16 16 16 16 16 16
100 125 50 50 50 50 50 50 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
Backup limit values indicated in kA
8 S800, SMISSLINE with ABB Products | Back-up and Selectivity tables
Char. I cu [kA]
Downstream
Icn [kA] S400M S450M FS401M FS403M
B, D
10
In [A] 4*…16 20 25 32 40 50 63
* for B characteristic only Upstream Char. DownI cu [kA] stream I n [A] 50 0.5…2 25 3...20 25 S400M 32 C, K S450M 40 15 50 63
25 50
25 50 50
32 50 50
32 50 50
40 50 50 50
40 50 50 50
S800S B, C, D, K 50 50 63 50 50 50 50 50 50 50 50 50
S800S B, C, D, K 50 50 63 50 50 50 50 50 50 50 50 50
Back-up protection S800S – SN201 S800S – SN201 @ 230/400 V Upstream Char. Icu [kA]
Downstream
SN201
B, D
10
In [A] 6 10 16 20 25 32 40
25 50 50 50
32 50 50 50 50
40 50 50 50 50 50
S800S B, C, D, K 50 50 63 50 50 50 50 50 50 50 50 50 50 50 50 50
80 50 50 50 50 50 50 50
100 125 50 50 50 50 50 50 50 50 50 50 50 50 50 50
S800S B, C, D, K 50 50 63 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
80 50 50 50 50 50 50 50 50 50
100 125 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
S800S B, C, D, K 50 50 63 25 18 25 18 25 18 25 18 25 18 25 18 25 18 25 18 18
80 15 15 15 15 15 15 15 15 15
100 125 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
S800S B, C, D, K 50 50 63 50 50 50 50 50 50 50 50 50 50 50 50 50
80 50 50 50 50 50 50 50
100 125 50 50 50 50 50 50 50 50 50 50 50 50 50 50
S800S B, C, D, K 50 50 63 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
80 50 50 50 50 50 50 50 50
100 125 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
S800S – SN201 @ 230/400 V Upstream Char. Icu [kA]
Downstream
SN201
C
10
In [A] 2 4 6 10 16 20 25 32 40
25 50 50 50 50 50
32 50 50 50 50 50 50
40 50 50 50 50 50 50 50
S800S – SN201 L @230/400 V Upstream Char. Icu [kA]
Downstream
SN201 L
B, C
6
In [A] 2 4 6 10 16 20 25 32 40
25 50 50 50 50 50
32 40 40 40 40 40 40
40 25 25 25 25 25 25 25
S800S – SN201 M @ 230/400 V Upstream Char. Icu [kA]
Downstream
SN201 M
B
10
In [A] 6 10 16 20 25 32 40
25 50 50 50
32 50 50 50 50
40 50 50 50 50 50
S800S - SN201 M @ 230/400 V Upstream Char. Icu [kA]
Downstream
SN201 M
C
10
In [A] 2 4 6 10 16 20 25 32
25 50 50 50 50 50
32 50 50 50 50 50 50
40 50 50 50 50 50 50 50
Back-up and Selectivity tables | S800, SMISSLINE with ABB Products 9
Back-up protection S800N – S60, -S200, -S200M, -S200P S800N – S60 @ 230/400 V
S800N – S200M @ 230/400 V
Upstream Char. Icu [kA]
Downstream
S60
C
6
In [A] 2 4 6 8 10 13 16 20 25 32 40 50 63
25 36 36 36 36 36 36 36
32 36 36 36 36 36 36 36 36
40 36 36 36 36 36 36 36 36 36
S800N B, C, D 36 50 63 25 18 25 18 25 18 25 18 25 18 25 18 25 18 25 18 25 18 25 18 18
Upstream Char. 80 15 15 15 15 15 15 15 15 15 15 15 15
100 125 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
Icu [kA]
Downstream
S200M
B
15
Upstream Icu [kA]
Downstream
S200
B
10
In [A] 6 10 13 16 20 25 32 40 50 63
25 36 36 36 36
32 36 36 36 36 36
40 36 36 36 36 36 36
Upstream Char. Icu [kA]
Downstream
S200
C
10
In [A] 0.5…6 8 10 13 16 20 25 32 40 50 63
25 36 36 36 36 36
32 36 36 36 36 36 36
40 36 36 36 36 36 36 36
S800N B, C, D 36 50 63 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36
S800N B, C, D 36 50 63 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36
100 125 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36
100 125 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36
C
15
Upstream Char. Icu [kA]
Downstream
S200L
C
6
In [A] 6...8 10 13 16 20 25 32 40
25 36 36 36 36
32 36 36 36 36 36
40 36 36 36 36 36 36
S800N B, C, D 36 50 63 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36
80 36 36 36 36 36 36 36 36
100 125 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36
Backup limit values indicated in kA
10 S800, SMISSLINE with ABB Products | Back-up and Selectivity tables
In [A] 0.5…16 20 25 32 40 50 63
25 36
32 36 36
40 36 36 36
S800N B, C, D 36 50 63 36 36 36 36 36 36 36 36 36
80 36 36 36 36 36 36
100 125 36 36 36 36 36 36 36 36 36 36 36 36 36 36
80 36 36 36 36 36 36
100 125 36 36 36 36 36 36 36 36 36 36 36 36 36 36
80 36 36 36 36 36 36
100 125 36 36 36 36 36 36 36 36 36 36 36 36 36 36
80 36 36 36 36 36 36
100 125 36 36 36 36 36 36 36 36 36 36 36 36 36 36
S800N – S200P @ 230/400 V Upstream Char. Icu [kA]
Downstream S200P
B
25
In [A] 6…16 20 25 32 40 50 63
25 36
32 36 36
40 36 36 36
Upstream Char. Icu [kA]
Downstream S200P
C
25
15
S800N – S200L @ 230/400 V
40 36 36 36
Icu [kA]
Downstream
15 80 36 36 36 36 36 36 36 36 36 36
32 36 36
Upstream
S200M
80 36 36 36 36 36 36 36 36 36
25 36
Char.
S800N – S200 @ 230/400 V Char.
In [A] 6…16 20 25 32 40 50 63
S800N B, C, D 36 50 63 36 36 36 36 36 36 36 36 36
In [A] 0.5…16 20 25 32 40 50 63
25 36
32 36 36
40 36 36 36
S800N B, C, D 36 50 63 36 36 36 36 36 36 36 36 36
S800N B, C, D 36 50 63 36 36 36 36 36 36 36 36 36
Back-up protection S800N – S280, -S400E, -S400M S800N – S280 @ 230/400 V
S800N – S400E @ 230/400 V
Upstream Char. Icu [kA]
Downstream
10
S280
B
25
15 10
In [A] 6 10 13 16 20 25 32 40 50 63
25 36 36 36 36
32 36 36 36 36 36
40 36 36 36 36 36 36
Upstream Char. Icu [kA]
Downstream
10
S280
C
25
15 10
In [A] 3 4 6 8 10 13 16 20 25 32 40 50 63
25 36 36 36 36 36 36 36
32 36 36 36 36 36 36 36 36
40 36 36 36 36 36 36 36 36 36
Upstream Char. Icu [kA]
Downstream
10
S280
K, Z
25
15 10
In [A] 3 4 6 8 10 13 16 20 25 32 40 50 63
25 36 36 36 36 36 36 36
32 36 36 36 36 36 36 36 36
40 36 36 36 36 36 36 36 36 36
S800N B, C, D 36 50 63 36 36 25 20 25 20 25 20 25 20 25 20 25 20 20
S800N B, C, D 36 50 63 36 36 36 36 36 36 25 20 25 20 25 20 25 20 25 20 25 20 25 20 20
S800N B, C, D 36 50 63 36 36 36 36 36 36 25 20 25 20 25 20 25 20 25 20 25 20 25 20 20
Upstream Char. 80 36 16 16 16 16 16 16 16 16
100 125 36 36 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
Icu [kA]
Downstream
Icn [kA]
S400E
B
6
In [A] 6 10 13 16 20 25 32 40 50 63
25 36 36 36 36
32 36 36 36 36 36
40 36 36 36 36 36 36
Upstream Char. 80 36 36 36 16 16 16 16 16 16 16 16 16
100 125 36 36 36 36 36 36 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
Icu [kA]
Downstream
Icn [kA]
S400E
C
6
In [A] 0.5...6 8 10 13 16 20 25 32 40 50 63
25 36 36 36 36 36
32 36 36 36 36 36 36
40 36 36 36 36 36 36 36
S800N B, C, D 36 50 63 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36
S800N B, C, D 36 50 63 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36
80 36 36 36 36 36 36 36 36 36
100 125 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36
80 36 36 36 36 36 36 36 36 36 36
100 125 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36
80 36 36 36 36 36 36
100 125 36 36 36 36 36 36 36 36 36 36 36 36 36 36
80 36 36 36 36 36 36
100 125 36 36 36 36 36 36 36 36 36 36 36 36 36 36
S800N – S400M @ 230/400 V Upstream 80 36 36 36 16 16 16 16 16 16 16 16 16
100 125 36 36 36 36 36 36 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
Char. I cu [kA]
Downstream
Icn [kA] S400M S450M FS401MB FS403MB
B, D
10
In [A] 4*…16 20 25 32 40 50 63
25 36
32 36 36
40 36 36 36
S800N B, C, D 36 50 63 36 36 36 36 36 36 36 36 36
* for B characteristic only Upstream Char. I cn [kA]
Downstream
50 25 S400M S450M FS401MC FS451MC
C, K
15
I n [A] 0.5...2 3...20 25 32 40 50 63
25 36 36
32 36 36
40 36 36 36
S800N B, C, D 36 50 63 36 36 36 36 36 36 36 36 36
Backup limit values indicated in kA
Back-up and Selectivity tables | S800, SMISSLINE with ABB Products 11
Back-up protection S800N – SN201 S800N – SN201 @ 230/400 V Upstream Char. Icu [kA]
Downstream
SN201
B, D
10
In [A] 6 10 16 20 25 32 40
25 36 36 36
32 36 36 36 36
40 36 36 36 36 36
S800N B, C, D 36 50 63 36 36 36 36 36 36 36 36 36 36 36 36 36
80 36 36 36 36 36 36 36
100 125 36 36 36 36 36 36 36 36 36 36 36 36 36 36
S800N B, C, D 36 50 63 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36
80 36 36 36 36 36 36 36 36 36
100 125 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36
S800N B, C, D 36 50 63 25 18 25 18 25 18 25 18 25 18 25 18 25 18 25 18 18
80 15 15 15 15 15 15 15 15 15
100 125 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
S800N B, C, D 36 50 63 36 36 36 36 36 36 36 36 36 36 36 36 36
80 36 36 36 36 36 36 36
100 125 36 36 36 36 36 36 36 36 36 36 36 36 36 36
S800N B, C, D 36 50 63 36 36 36 36 36 36 36 36 36 36 36 36 36 36
80 36 36 36 36 36 36 36
100 125 36 36 36 36 36 36 36 36 36 36 36 36 36 36
S800N – SN201 @ 230/400 V Upstream Char. Icu [kA]
Downstream
SN201
C
10
In [A] 2 4 6 10 16 20 25 32 40
25 36 36 36 36 36
32 36 36 36 36 36 36
40 36 36 36 36 36 36 36
S800N – SN201L @ 230/400 V Upstream Char. Icu [kA]
Downstream
SN201 L
B, C
6
In [A] 2 4 6 10 16 20 25 32 40
25 36 36 36 36 36
32 36 36 36 36 36 36
40 25 25 25 25 25 25 25
S800N – SN201M @ 230/400 V Upstream Char. Icu [kA]
Downstream
SN201 M
B
10
In [A] 6 10 16 20 25 32 40
25 36 36 36
32 36 36 36 36
40 36 36 36 36 36
S800N – SN201M @230/400 V Upstream Char. Icu [kA]
Downstream
SN201 M
C
10
In [A] 2 4 6 10 16 20 25
25 36 36 36 36 36
32 36 36 36 36 36 36
40 36 36 36 36 36 36 36
12 S800, SMISSLINE with ABB Products | Back-up and Selectivity tables
Back-up protection S800C – S60, -S200, -S200M, -S200P S800C – S60 @ 230/400 V
S800C – S200M @ 230/400 V
Upstream Char. Icu [kA]
Downstream
S60
C
6
In [A] 2 4 6 8 10 13 16 20 25 32 40 50 63
25 25 25 25 25 25 25 25
32 25 25 25 25 25 25 25 25
40 25 25 25 25 25 25 25 25 25
S800C B, C, D 25 50 63 25 18 25 18 25 18 25 18 25 18 25 18 25 18 25 18 25 18 25 18 18
Upstream Char. 80 15 15 15 15 15 15 15 15 15 15 15 15
100 125 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
Icu [kA]
Downstream
S200M
B
15
Upstream Icu [kA]
Downstream
S200
B
10
In [A] 6 10 13 16 20 25 32 40 50 63
25 25 25 25 25
32 25 25 25 25 25
40 25 25 25 25 25 25
Upstream Char. Icu [kA]
Downstream
S200
C
10
In [A] 0.5…6 8 10 13 16 20 25 32 40 50 63
25 25 25 25 25 25
32 25 25 25 25 25 25
40 25 25 25 25 25 25 25
S800C B, C, D 25 50 63 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25
S800C B, C, D 25 50 63 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25
100 125 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25
100 125 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25
40 25 25 25
Icu [kA]
Downstream
C
15
In [A] 0.5…16 20 25 32 40 50 63
25 25
32 25 25
40 25 25 25
S800C B, C, D 25 50 63 25 25 25 25 25 25 25 25 25
80 25 25 25 25 25 25
100 125 25 25 25 25 25 25 25 25 25 25 25 25 25 25
80 25 25 25 25 25 25
100 125 25 25 25 25 25 25 25 25 25 25 25 25 25 25
80 25 25 25 25 25 25
100 125 25 25 25 25 25 25 25 25 25 25 25 25 25 25
80 25 25 25 25 25 25
100 125 25 25 25 25 25 25 25 25 25 25 25 25 25 25
S800C – S200P @ 230/400 V Upstream Char. Icu [kA]
Downstream S200P
B
25
15 80 25 25 25 25 25 25 25 25 25 25
32 25 25
Upstream
S200M
80 25 25 25 25 25 25 25 25 25
25 25
Char.
S800C – S200 @ 230/400 V Char.
In [A] 6…16 20 25 32 40 50 63
S800C B, C, D 25 50 63 25 25 25 25 25 25 25 25 25
In [A] 6…16 20 25 32 40 50 63
25 25
32 25 25
40 25 25 25
Upstream Char. Icu [kA]
Downstream S200P
C
25
15
In [A] 0.5…16 20 25 32 40 50 63
25 25
32 25 25
40 25 25 25
S800C B, C, D 25 50 63 25 25 25 25 25 25 25 25 25
S800C B, C, D 25 50 63 25 25 25 25 25 25 25 25 25
S800C – S200L @ 230/400 V Upstream Char. Icu [kA]
Downstream
S200L
C
6
In [A] 6...8 10 13 16 20 25 32 40
25 25 25 25 25
32 25 25 25 25 25
40 25 25 25 25 25 25
S800C B, C, D 25 50 63 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25
80 25 25 25 25 25 25 25 25
100 125 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25
Backup limit values indicated in kA
Back-up and Selectivity tables | S800, SMISSLINE with ABB Products 13
Back-up protection S800C – S280, -S400E, -S400M S800C – S280 @ 230/400 V
S800C – S400E @ 230/400 V
Upstream Char. Icu [kA]
Downstream
10
S280
B
25
15 10
In [A] 6 10 13 16 20 25 32 40 50 63
25 25 25 25 25
32 25 25 25 25 25
40 25 25 25 25 25 25
Upstream Char. Icu [kA]
Downstream
10
S280
C
25
15 10
In [A] 3 4 6 8 10 13 16 20 25 32 40 50 63
25 25 25 25 25 25 25 25
32 25 25 25 25 25 25 25 25
40 25 25 25 25 25 25 25 25 25
Upstream Char. Icu [kA]
Downstream
10
S280
K, Z
25
15 10
In [A] 3 4 6 8 10 13 16 20 25 32 40 50 63
25 25 25 25 25 25 25 25
32 25 25 25 25 25 25 25 25
40 25 25 25 25 25 25 25 25 25
S800C B, C, D 25 50 63 25 25 25 20 25 20 25 20 25 20 25 20 25 20 20
S800C B, C, D 25 50 63 25 25 25 25 25 25 25 20 25 20 25 20 25 20 25 20 25 20 25 20 20
S800C B, C, D 25 50 63 25 25 25 25 25 25 25 20 25 20 25 20 25 20 25 20 25 20 25 20 20
Upstream Char. 80 25 16 16 16 16 16 16 16 16
100 125 25 25 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
Icu [kA]
Downstream
Icn [kA]
S400E
B 6
In [A] 6 10 13 16 20 25 32 40 50 63
25 25 25 25 25
32 25 25 25 25 25
40 25 25 25 25 25 25
Upstream Char. 80 25 25 25 16 16 16 16 16 16 16 16 16
100 125 25 25 25 25 25 25 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
80 25 25 25 16 16 16 16 16 16 16 16 16
100 125 25 25 25 25 25 25 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
Backup limit values indicated in kA
14 S800, SMISSLINE with ABB Products | Back-up and Selectivity tables
Icu [kA]
Downstream
Icn [kA]
S400E
C
6
In [A] 0.5...6 8 10 13 16 20 25 32 40 50 63
25 25 25 25 25 25
32 25 25 25 25 25 25
40 25 25 25 25 25 25 25
S800C B, C, D 25 50 63 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25
S800C B, C, D 25 50 63 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25
80 25 25 25 25 25 25 25 25 25
100 125 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25
80 25 25 25 25 25 25 25 25 25 25
100 125 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25
Back-up protection S800C – S400M S800C – S400M @ 230/400 V Upstream Char. Icu [kA]
Downstream
Icn [kA] S400M S450M
B, D 10
In [A] 4*…16 20 25 32 40 50 63
25 25
32 25 25
40 25 25 25
S800C B, C, D 25 50 63 25 25 25 25 25 25 25 25 25
80 25 25 25 25 25 25
100 125 25 25 25 25 25 25 25 25 25 25 25 25 25 25
80 25 25 25 25 25
100 125 25 25 25 25 25 25 25 25 25 25 25 25
80 25 25 25 25 25
100 125 25 25 25 25 25 25 25 25 25 25 25 25
* for B characteristic only Upstream Char. Icu [kA]
Downstream
25 S400M S450M
C 15
In [A] 3...20 25 32 40 50 63
25 25
32 25
40 25 25
Upstream Char. Icu [kA]
Downstream
25 S400M S450M
K 10
In [A] 3...20 25 32 40 50 63
25 25
32 25
40 25 25
S800C B, C, D 25 50 63 25 25 25 25 25 25 25
S800C B, C, D 25 50 63 25 25 25 25 25 25 25
Backup limit values indicated in kA
Back-up and Selectivity tables | S800, SMISSLINE with ABB Products 15
Back-up protection S800C – SN201 S800C – SN201 @ 230/400 V Upstream Char. Icu [kA]
Downstream
SN201
B, D
10
In [A] 6 10 16 20 25 32 40
25 25 25 25
32 25 25 25 25
40 25 25 25 25 25
S800C B, C, D, K 25 50 63 25 25 25 25 25 25 25 25 25 25 25 25 25
80 25 25 25 25 25 25 25
100 125 25 25 25 25 25 25 25 25 25 25 25 25 25 25
S800C B, C, D, K 25 50 63 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25
80 25 25 25 25 25 25 25 25 25
100 125 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25
S800C B, C, D, K 25 50 63 25 18 25 18 25 18 25 18 25 18 25 18 25 18 25 18 18
80 15 15 15 15 15 15 15 15 15
100 125 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
S800C B, C, D, K 25 50 63 25 25 25 25 25 25 25 25 25 25 25 25 25
80 25 25 25 25 25 25 25
100 125 25 25 25 25 25 25 25 25 25 25 25 25 25 25
S800C B, C, D, K 25 50 63 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25
80 25 25 25 25 25 25 25 25
100 125 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25
S800C – SN201 @ 230/400 V Upstream Char. Icu [kA]
Downstream
SN201
C
10
In [A] 2 4 6 10 16 20 25 32 40
25 25 25 25 25 25
32 25 25 25 25 25 25
40 25 25 25 25 25 25 25
S800C – SN201L @ 230/400 V Upstream Char. Icu [kA]
Downstream
SN201L
B, C
6
In [A] 2 4 6 10 16 20 25 32 40
25 25 25 25 25 25
32 25 25 25 25 25 25
40 25 25 25 25 25 25 25
S800C – SN201M @ 230/400 V Upstream Char. Icu [kA]
Downstream
SN201M
B
10
In [A] 6 10 16 20 25 32 40
25 25 25 25
32 25 25 25 25
40 25 25 25 25 25
S800C – SN201M @ 230/400 V Upstream Char. Icu [kA]
Downstream
SN201M
C
10
In [A] 2 4 6 10 16 20 25 32
25 25 25 25 25 25
32 25 25 25 25 25 25
40 25 25 25 25 25 25 25
16 S800, SMISSLINE with ABB Products | Back-up and Selectivity tables
Back-up protection S800B – S200 S800B – S200 @ 230/400 V Upstream
S800B B, C, D, K
Char. Icu [kA]
Downstream
S200
B
In [A] 6 10 13 16 20 25 32 40 50 63
10
32 16 16 16 16 16
40 16 16 16 16 16 16
Upstream
63 16 16 16 16 16 16 16 16
80 16 16 16 16 16 16 16 16 16 16
100 125* 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
S800B B, C, D, K
Char. Icu [kA]
Downstream
S200
50 16 16 16 16 16 16 16
C, D K, Z
10
In [A] 0.5…6 8 10 13 16 20 25 32 40 50 63
32 16 16 16 16 16 16
40 16 16 16 16 16 16 16
50 16 16 16 16 16 16 16 16
63 16 16 16 16 16 16 16 16 16
80 16 16 16 16 16 16 16 16 16 16 16
100 125* 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
* only S800B-B,C back-up values indicated in kA
S800B – S200M @ 230/400 V Upstream
S800B B, C, D, K
Char. Icu [kA]
Downstream
15 S200M
B
10
In [A] 6 10 13 16 20 25 32 40 50 63
32 16 16 16 16 16
40 16 16 16 16 16 16
Upstream
63 16 16 16 16 16 16 16 16
80 16 16 16 16 16 16 16 16 16 16
100 125* 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
S800B B, C, D, K
Char. Icu [kA]
Downstream
S200
50 16 16 16 16 16 16 16
C, D K, Z
15
10
In [A] 0.5…6 8 10 13 16 20 25 32 40 50 63
32 16 16 16 16 16 16
40 16 16 16 16 16 16 16
50 16 16 16 16 16 16 16 16
63 16 16 16 16 16 16 16 16 16
80 16 16 16 16 16 16 16 16 16 16 16
100 125* 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
* only S800B-B,C
Back-up and Selectivity tables | S800, SMISSLINE with ABB Products 17
Back-up protection S800B – S400 S800B – S400E @ 230/400 V Upstream
S800B B, C, D, K
Char. Icu [kA]
Downstream
S400E
B, C
In [A] 6 8 10 13 16 20 25 32 40 50 63
6
32 16 16 16 16 16 16
40 16 16 16 16 16 16 16
50 16 16 16 16 16 16 16 16
63 16 16 16 16 16 16 16 16 16
80 16 16 16 16 16 16 16 16 16 16 16
100 125* 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
* only S800B-B,C back-up values indicated in kA
S800B – S400M @ 230/400 V Upstream
S800B B, C, D, K
Char. Icu [kA]
Downstream
S400M
B, D
10
In [A] 6** 8** 10 13 16 20 25 32 40 50 63
32 16 16 16 16 16 16
40 16 16 16 16 16 16 16
Upstream
80 16 16 16 16 16 16 16 16 16 16 16
100 125* 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
Icu [kA]
Downstream
C
10
In [A] 2 3 4 6 8 10 13 16 20 25 32 40 50 63
32 16 16 16 16 16 16 16 16 16
40 16 16 16 16 16 16 16 16 16 16
Upstream
50 16 16 16 16 16 16 16 16 16 16 16
63 16 16 16 16 16 16 16 16 16 16 16 16
80 16 16 16 16 16 16 16 16 16 16 16 16 16 16
100 125* 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
S800B B, C, D, K
Char. Icu [kA]
Downstream
S400M
63 16 16 16 16 16 16 16 16 16
S800B B, C, D, K
Char.
S400M
50 16 16 16 16 16 16 16 16
K
10
In [A] 0.5..6 8 10 13 16 20 25 32 40 50 63
32 16 16 16 16 16 16
40 16 16 16 16 16 16 16
50 16 16 16 16 16 16 16 16
63 16 16 16 16 16 16 16 16 16
80 16 16 16 16 16 16 16 16 16 16 16
100 125* 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
* only S800B-B,C ** only S400M-B
18 S800, SMISSLINE with ABB Products | Back-up and Selectivity tables
Back-up protection S800B – SN201 S800B – SN201 @ 230 V (Two-pole circuit-breakers) Upstream
S800B B, C, D, K
Char. Icu [kA]
Downstream
SN201
B, D
10
In [A] 6 10 16 20 25 32 40
32 16 16 16 16
40 16 16 16 16 16
Upstream
C
10
In [A] 2 4 6 10 13 16 20 25 32 40
32 16 16 16 16 16 16 16
40 16 16 16 16 16 16 16 16
Upstream
50 16 16 16 16 16 16 16 16 16
63 16 16 16 16 16 16 16 16 16 16
80 16 16 16 16 16 16 16 16 16 16
100 125* 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
Icu [kA]
Downstream
B, C
6
In [A] 2 4 6 10 16 20 25 32 40
32 16 16 16 16 16 16
40 16 16 16 16 16 16 16
Upstream
50 16 16 16 16 16 16 16 16
63 16 16 16 16 16 16 16 16 16
80 15 15 15 15 15 15 15 15 15
100 125* 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
S800B B, C, D, K
Char. Icu [kA]
Downstream
B
10
In [A] 6 10 16 20 25 32 40
32 16 16 16 16
40 16 16 16 16 16
Upstream
50 16 16 16 16 16 16
63 16 16 16 16 16 16 16
80 16 16 16 16 16 16 16
100 125* 16 16 16 16 16 16 16 16 16 16 16 16 16 16
S800B B, C, D, K
Char. Icu [kA]
Downstream
SN201 M
100 125* 16 16 16 16 16 16 16 16 16 16 16 16 16 16
S800B B, C, D, K
Char.
SN201 M
80 16 16 16 16 16 16 16
Icu [kA]
Downstream
SN201 L
63 16 16 16 16 16 16 16
S800B B, C, D, K
Char.
SN201
50 16 16 16 16 16 16
C
10
In [A] 2 4 6 10 16 20 25 32 40
32 16 16 16 16 16 16
40 16 16 16 16 16 16 16
50 16 16 16 16 16 16 16 16
63 16 16 16 16 16 16 16 16 16
80 16 16 16 16 16 16 16 16 16
100 125 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
* only S800B-B,C back-up values indicated in kA
Back-up and Selectivity tables | S800, SMISSLINE with ABB Products 19
Back-up compliant to IEC 60947-2 S800U – S60, -S200, -S200L, -S200M S800U – S60 @ 230/400 V
S800U – S200L @ 230/400 V
Upstream Char. Icu [kA]
Downstream
S60
C
6
In [A] 2 4 8 10 13 16 20 25 32 40 50 63
25 50 50 50 50 50 50
32 50 50 50 50 50 50 50
40 50 50 50 50 50 50 50 50
S800U K, Z 50 50 63 25 18 25 18 25 18 25 18 25 18 25 18 25 18 25 18 25 18 18
Upstream Char. 80 15 15 15 15 15 15 15 15 15 15 15
100 125 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
S800U – S200 @ 230/400 V Char.
S200
Icu [kA]
B
10
S200L
C 6
In [A] 6...8 10 13 16 20 25 32 40
25 50 50 50 50
32 50 50 50 50 50
40 50 50 50 50 50 50
In [A] 6 10 13 16 20 25 32 40 50 63
25 50 50 50 50
32 50 50 50 50 50
40 50 50 50 50 50 50
S800U K, Z 50 50 63 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
Upstream Char. 80 50 50 50 50 50 50 50 50 50
100 125 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
Icu [kA]
Downstream
S200M
B 15
In [A] 6...16 20 25 32 40 50 63
25 50
32 50 50
40 50 50 50
Upstream Char. Upstream Char. Icu [kA]
Downstream
S200
B
10
80 50 50 50 50 50 50 50 50
100 125 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
80 50 50 50 50 50 50
100 125 50 50 50 50 50 50 50 50 50 50 50 50 50 50
80 50 50 50 50 50 50
100 125 50 50 50 50 50 50 50 50 50 50 50 50 50 50
S800U – S200M @ 230/400 V
Upstream Downstream
Icu [kA]
Downstream
S800U K, Z 50 50 63 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
In [A] 0.5...6 8 10 13 16 20 25 32 40 50 63
25 50 50 50 50 50
32 50 50 50 50 50 50
40 50 50 50 50 50 50 50
S800U K, Z 50 50 63 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
Icu [kA]
Downstream
80 50 50 50 50 50 50 50 50 50 50
100 125 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
Backup limit values indicated in kA
20 S800, SMISSLINE with ABB Products | Back-up and Selectivity tables
S200M
C 15
In [A] 0.5...16 20 25 32 40 50 63
25 50
32 50 50
40 50 50 50
S800U K, Z 50 50 63 50 50 50 50 50 50 50 50 50
S800U K, Z 50 50 63 50 50 50 50 50 50 50 50 50
Back-up compliant to IEC 60947-2 S800U – S200P S800U – S200P @ 230/400 V Upstream Char. Icu [kA]
Downstream
25 S200P
B 15
In [A] 6...16 20 25 32 40 50 63
25 50
32 50 50
40 50 50 50
Upstream Char. Icu [kA]
Downstream
25 S200P
C 15
In [A] 0.5...16 20 25 32 40 50 63
25 50
32 50 50
40 50 50 50
S800U K, Z 50 50 63 50 50 50 50 50 50 50 50 50
S800U K, Z 50 50 63 50 50 50 50 50 50 50 50 50
80 50 50 50 50 50 50
100 125 50 50 50 50 50 50 50 50 50 50 50 50 50 50
80 50 50 50 50 50 50
100 125 50 50 50 50 50 50 50 50 50 50 50 50 50 50
Backup limit values indicated in kA
Back-up and Selectivity tables | S800, SMISSLINE with ABB Products 21
Back-up compliant to IEC 60947-2 S800U – S280, -S400E, -S400M S800U – S280 @ 230/400 V
S800U – S400E @ 230/400 V
Upstream Char. Icu [kA]
Downstream
10
25
S280
B
15 10
In [A] 6 10 13 16 20 25 32 40 50 63
25 50 50 50 50
32 50 50 50 50 50
40 50 50 50 50 50 50
Upstream Char. Icu [kA]
Downstream
10
S280 25
C
15 10
In [A] 3 4 6 8 10 13 16 20 25 32 40 50 63
25 50 50 50 50 50 50 50
32 50 50 50 50 50 50 50 50
40 50 50 50 50 50 50 50 50 50
Upstream Char. Icu [kA]
Downstream
10
S280 25
K, Z
15 10
In [A] 3 4 6 8 10 13 16 20 25 32 40 50 63
25 50 50 50 50 50 50 50
32 50 50 50 50 50 50 50 50
40 50 50 50 50 50 50 50 50 50
S800U K, Z 50 50 63 50 50 25 20 25 20 25 20 25 20 25 20 25 20 20
S800U K, Z 50 50 63 50 50 25 20 25 20 25 20 25 20 25 20 25 20 25 20 25 20 25 20 20
S800U K, Z 50 50 63 50 50 25 20 25 20 25 20 25 20 25 20 25 20 25 20 25 20 25 20 20
Upstream Char. 80 50 16 16 16 16 16 16 16 16
100 125 50 50 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
Icu [kA]
Downstream
Icn [kA]
S400E
B
6
In [A] 6 10 13 16 20 25 32 40 50 63
25 50 50 50 50
32 50 50 50 50 50
40 50 50 50 50 50 50
Upstream Char. 80 50 16 16 16 16 16 16 16 16 16 16 16
100 125 50 50 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
Icu [kA]
Downstream
Icn [kA]
S400E
C
6
In [A] 0.5...6 8 10 13 16 20 25 32 40 50 63
25 50 50 50 50 50
32 50 50 50 50 50 50
40 50 50 50 50 50 50 50
S800U K, Z 50 50 63 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
S800U K, Z 50 50 63 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
80 50 50 50 50 50 50 50 50 50
100 125 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
80 50 50 50 50 50 50 50 50 50 50
100 125 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
80 50 50 50 50 50 50
100 125 50 50 50 50 50 50 50 50 50 50 50 50 50 50
80 50 50 50 50 50
100 125 50 50 50 50 50 50 50 50 50 50 50 50
80 50 50 50 50 50
100 125 50 50 50 50 50 50 50 50 50 50 50 50
S800U – S400M @ 230/400 V Upstream Char. 80 50 16 16 16 16 16 16 16 16 16 16 16
100 125 50 50 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
Icu [kA]
Downstream
Icn [kA] S400M S450M
B, D 10
In [A] 4*...16 20 25 32 40 50 63
25 50
32 50 50
40 50 50 50
* only applies to B characteristic
Upstream Char. Icu [kA]
Downstream
25 S400M S450M
C 15
In [A] 3...20 25 32 40 50 63
25 50
32 50
40 50 50
Upstream Char. Icu [kA]
Downstream
25 S400M S450M
K 10
Backup limit values indicated in kA
22 S800, SMISSLINE with ABB Products | Back-up and Selectivity tables
S800U K, Z 50 50 63 50 50 50 50 50 50 50 50 50
In [A] 3...20 25 32 40 50 63
25 50
32 50
40 50 50
S800U K, Z 50 50 63 50 50 50 50 50 50 50
S800U K, Z 50 50 63 50 50 50 50 50 50 50
Back-up compliant to UL 489 Tmax/Fuse – S800U acc. to UL489 Class J Fuse – S800U (1-pole) @ 240 V AC Downstream
Char.
S800U
K, Z
Upstream In [kA] Icu [A] 10...80 30 10...100
Fuse max. 250 30 30
max. 250 30 30
Class J Fuse – S800U (multipole) @ 240 V AC Downstream
Char.
S800U
K, Z
Upstream In [kA] Icu [A] 10...80 50 10...100
Fuse max. 250 50 50
max. 250 50 50
Sace Tmax – S800U (1-pole) @ 240 V AC Upstream Icu [A] Downream S800U
Char. K, Z
30
In [A] 10...80 90...100
T4 N 65 20...250 30 30
T4 S 100 20...250 30 30
T4 H 150 20...250 30 30
T4 L 200 20...250 30 30
T4 V 200 20...250 30 30
T5 N 65 max. 600 30 30
T5 S 100 max. 600 30 30
T5 H 150 max. 600 30 30
T5 L 200 max. 600 30 30
T5 V 200 max. 600 30 30
T4 N 65 20...250 50 50
T4 S 100 20...250 50 50
T4 H 150 20...250 50 50
T4 L 200 20...250 50 50
T4 V 200 20...250 50 50
T5 N 65 max. 600 50 50
T5 S 100 max. 600 50 50
T5 H 150 max. 600 50 50
T5 L 200 max. 600 50 50
T5 V 200 max. 600 50 50
Sace Tmax – S800U (multipole) @ 240 V AC Upstream Icu [kA] Downstream
Char.
S800U
K, Z
50
In [A] 10...80 90...100
Backup limit values indicated in kA
Back-up and Selectivity tables | S800, SMISSLINE with ABB Products 23
Back-up protection Tmax /XT – S800 Tmax – S800 @ 415 V
Downstream
Char.
ln [A]
Upstream
T1
T1
T2
T4
Version
B
C
N
S
H
L
L
V
lcu [kA]
16
25
36
50
70
85
120
200
S800S
B, C, D, K
6…125
50
S800N
B, C, D
6…125
36
S800C
B, C, D, K
10…125
25
T1
T2
36
T3
36
36
T4
T2
36
T3
T4
T2
T4
T4
70
70
85
120
200
50
50
50
70
70
85
120
200
50
50
50
70
70
85
120
200
XT – S800 @ 415 V Upstream
XT1
XT1
Version
B
C
N
S
lcu [kA]
18
25
36
50
Downstream
Char.
ln [A]
S800S
B, C, D, K
6…125
50
S800N
B, C, D
6…125
36
S800C
B, C, D, K
10…125
25
XT1
36
XT2
36
24 S800, SMISSLINE with ABB Products | Back-up and Selectivity tables
XT3
36
XT4
36
XT1
XT2
XT3
XT4
XT1
XT2
XT4
XT2
H
XT4
XT2
XT4
120
120
150
L 70
V
70
70
70
120
120
150
150
50
50
50
50
70
70
70
120
120
150
150
50
50
50
50
70
70
70
120
120
150
150
Back-up protection S800 – S400M S800S – S400M @ 254/440 V
Downstream
S400M S450M
Char.
C, K
Upstream Char. Icu [kA] In [A] 15 0,5…2 10 3…10 13 16 20 25 6 32 40 50 63
25 30 30 30 30
32 30 30 30 30 30
40 30 30 30 30 30 30
S800S B, C, D, K 30 50 63 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30
80 30 30 30 30 30 30 30 30 30
100 125 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30
80 20 20 20 20 20 20 20 20 20
100 125 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20
S800N – S400M @ 254/440 V
Downstream
S400M S450M
Char.
C, K
Upstream Char. Icu [kA] In [A] 15 0,5…2 10 3…10 13 16 20 25 6 32 40 50 63
25 20 20 20 20
32 20 20 20 20 20
40 20 20 20 20 20 20
S800N B, C, D, K 20 50 63 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20
Back-up and Selectivity tables | S800, SMISSLINE with ABB Products 25
Selectivity Fuses gL/gG – S400/S450, FS401/451 In a low voltage distribution system service continuity is much desired. This means, that two or more in series connected overcurrent protection devices should operate selective in case of an overload or a short circuit. Selectivity is achieved, if only the protective device closest to the fault location operates. Selectivity between two protection devices is assured, if the let through energy of the downstream installed protection device does not reach the value of the melting energy of the upstream connected one. In case of a short circuit a selective interruption of the fault current is assured up to the values indicated in the tables. The information is based on the average operating curves of the upstream connected protection devices.
Fuse gL/gG – S400M @ 230/400 V Upstream
Downstream
S400M S450M FS401M FS403M FS451M FS453M
Char.
Fuse gL/gG
ln [A]
16
20
25
35
50
63
80
100
125
160
#2
1
1.2
4
>15 *
>15 *
>15 *
>15 *
>15 *
>15 *
>15 *
3
0.3
0.7
1.2
4.6
6
6
6
6
6
6
4
0.3
0.6
0.9
2.8
6
6
6
6
6
6
6
0.2
0.5
0.8
2
3.3
5.5
6
6
6
6
8
0.2
0.4
0.7
1.7
2.8
4.5
6
6
6
6
10
0.2
0.4
0.7
1.5
2.5
3.5
5
6
6
6
0.7
1.5
2.5
3.5
5
6
6
6
1.3
2
2.9
4.1
6
6
6
20
1.8
2.6
3.5
5
6
6
25
1.8
2.6
3.5
5
6
6
2.2
3
4
6
6
2.5
4
6
6
3.5
5
6
13
B, C
16
32 40 50/63
Fuse gL/gG – S400M @ 230/400 V Upstream
Downstream
Char.
Fuse gL/gG
l n [A]
16
20
25
35
50
63
80
100
125
160
#2
0.3
1.2
4
>15 *
>15 *
>15 *
>15 *
>15 *
>15 *
>15 *
3
0.3
0.7
1.2
4.6
6
6
6
6
6
6
4
0.3
0.6
0.9
2.8
6
6
6
6
6
6
0.7
1.7
3
5.9
6
6
6
6
1.3
2.2
3.6
6
6
6
6
1.7
2.5
4
6
6
6
2.2
3.1
4.6
6
6
16
3.1
4.6
6
6
20
2.6
3.5
6
6
3.5
6
6
5.5
6
6 8 10 S400M S450M
D, K
13
25 32 40
6
50/63
T = total selectivity up to breaking capacity of downstream miniature circuit breaker Selectivity limits are specified in kA
26 S800, SMISSLINE with ABB Products | Back-up and Selectivity tables
* only applies to IEC/EN 60947-2 characteristics C and K
Selectivity S400/S450 – S400/S450 S400/S450 – S400/S450 @ 230/400 V
S400/S450 – S400/S450 @ 230/400 V
B-Characteristic 6
6
13
16
20
25
32
40
50
63
In (in A)
0.04
0.05
0.06
0.08
0.1
0.13
0.16
0.2
0.25
6
0.05
0.06
10 B-Characteristic
C-Characteristic
10
13
0.08
0.1
0.13
0.16
0.2
0.25
0.08
0.1
0.13
0.16
0.2
0.25
0.1
0.13
0.16
0.2
0.25
0.13
0.16
0.2
0.25
0.16
0.2
0.25
0.2
0.25
32
0.25
40
16 20 25 32 40
4
6
10
13
16
20
25
32
40
50
63
0.075
0.1
0.1
0.2
0.2
0.24
0.3
0.38
0.47
0.1
0.1
0.2
0.2
0.24
0.3
0.38
0.47
0.2
0.2
0.24
0.3
0.38
0.47
0.2
0.24
0.3
0.38
0.47
0.24
0.3
0.38
0.47
0.3
0.38
0.47
0.38
0.47
10 B-Characteristic
In (in A)
13 16 20 25
50
50
63
63
0.47
C-Characteristic
6
10
13
16
20
25
32
40
50
63
In (in A)
0.5
0.02
0.04
0.05
0.06
0.08
0.1
0.13
0.16
0.2
0.25
0.5
4
6
10
0.030 0.045 0.075
13
16
20
25
32
40
50
63
0.1
0.1
0.2
0.2
0.24
0.3
0.38
0.47
1
0.02
0.04
0.05
0.06
0.08
0.1
0.13
0.16
0.2
0.25
1
0.030 0.045 0.075
0.1
0.1
0.2
0.2
0.24
0.3
0.38
0.47
2
0.02
0.04
0.05
0.06
0.08
0.1
0.13
0.16
0.2
0.25
2
0.030 0.045 0.075
0.1
0.1
0.2
0.2
0.24
0.3
0.38
0.47
3
0.04
0.05
0.06
0.08
0.1
0.13
0.16
0.2
0.25
3
0.045 0.075
0.1
0.1
0.2
0.2
0.24
0.3
0.38
0.47
4
0.04
0.05
0.06
0.08
0.1
0.13
0.16
0.2
0.25
4
0.075
0.1
0.1
0.2
0.2
0.24
0.3
0.38
0.47
0.06
0.08
6
0.075
0.1
0.1
0.2
0.2
0.24
0.3
0.38
0.47
0.1
0.2
0.2
0.24
0.3
0.38
0.47
0.2
0.2
0.24
0.3
0.38
0.47
0.2
0.24
0.3
0.38
0.47
0.24
0.3
0.38
0.47
0.3
0.38
0.47
0.38
0.47
6 10
C-Characteristic
C-Characteristic
B-Characteristic In (in A)
0.1
0.13
0.16
0.2
0.25
0.1
0.13
0.16
0.2
0.25
0.13
0.16
0.2
0.25
0.16
0.2
0.25
0.2
0.25
20
0.25
25
13 16 20 25
10 13 16
32
32
40
40
50
50
63
63
0.47
B-Characteristic 6
6
13
16
20
25
32
40
50
63
In (in A)
0.04
0.05
0.06
0.08
0.1
0.13
0.16
0.2
0.25
6
0.06
0.08
0.1
0.13
0.16
0.2
0.25
0.08
0.1
0.13
0.16
0.2
0.25
0.1
0.13
0.16
0.2
0.25
0.13
0.16
0.2
0.25
0.16
0.2
0.25
0.2
0.25
32
0.25
40
10 D-Characteristic
C-Characteristic
10
13 16 20 25 32 40
4
6
10
13
16
20
25
32
40
50
63
0.075
0.1
0.1
0.2
0.2
0.24
0.3
0.38
0.47
10 D-Characteristic
In (in A)
0.1
13
0.2
0.24
0.3
0.38
0.47
0.2
0.24
0.3
0.38
0.47
0.2
0.24
0.3
0.38
0.47
0.24
0.3
0.38
0.47
0.3
0.38
0.47
0.38
0.47
16 20 25
50
50
63
63
0.47
B-Characteristic
C-Characteristic
In (in A)
6
10
13
16
20
25
32
40
50
63
In (in A)
0.5
0.02
0.04
0.05
0.06
0.08
0.1
0.13
0.16
0.2
0.25
0.5
4
6
10
0.030 0.045 0.075
13
16
20
25
32
40
50
63
0.1
0.1
0.2
0.2
0.24
0.3
0.38
0.47
1
0.02
0.04
0.05
0.06
0.08
0.1
0.13
0.16
0.2
0.25
1
0.030 0.045 0.075
0.1
0.1
0.2
0.2
0.24
0.3
0.38
0.47
2
0.02
0.04
0.05
0.06
0.08
0.1
0.13
0.16
0.2
0.25
2
0.030 0.045 0.075
0.1
0.1
0.2
0.2
0.24
0.3
0.38
0.47
3
0.02
4 6 10 13 16 20 25 32 40
0.04
0.05
0.06
0.08
0.1
0.13
0.16
0.2
0.25
3
0.045 0.075
0.1
0.1
0.2
0.2
0.24
0.3
0.38
0.47
0.04
0.05
0.06
0.08
0.1
0.13
0.16
0.2
0.25
4
0.075
0.1
0.1
0.2
0.2
0.24
0.3
0.38
0.47
0.1
0.2
0.2
0.24
0.3
0.38
0.47
0.1
0.2
0.2
0.24
0.3
0.38
0.47
0.2
0.2
0.24
0.3
0.38
0.47
0.2
0.24
0.3
0.38
0.47
0.24
0.3
0.38
0.47
0.3
0.38
0.47
0.38
0.47
0.05
K-Characteristic
K-Characteristic
0.2 0.2
0.06
0.08
0.1
0.13
0.16
0.2
0.25
0.06
0.08
0.1
0.13
0.16
0.2
0.25
0.1
0.13
0.16
0.2
0.25
0.1
0.13
0.16
0.2
0.25
0.13
0.16
0.2
0.25
20
0.16
0.2
0.25
25
0.2
0.25
32
0.25
40
0.08
6 10 13 16
50
50
63
63
0.1
0.47
Back-up and Selectivity tables | S800, SMISSLINE with ABB Products 27
Selectivity S400/S450 – S400/S450 S400/S450 – S400/S450 @ 230/400 V
S400/S450 – S400/S450 @ 230/400 V K-Characteristic
In (in A)
4
6
10
13
16
20
25
32
40
50
63
In (in A)
6
0.06
0.08
0.14
0.18
0.22
0.28
0.35
0.45
0.56
0.7
0.88
6
0.22
0.28
0.35
0.45
0.56
0.7
0.88
10
0.28
0.35
0.45
0.56
0.7
0.88
0.35
0.45
0.56
0.7
0.88
0.45
0.56
0.7
0.88
0.56
0.7
0.88
0.7
0.88
32
0.88
40
10 13 16 20 25 32 40
B-Characteristic
B-Characteristic
D-Characteristic 4
6
10
13
16
20
25
32
40
50
63
0.1
0.13
0.16
0.2
0.25
0.32
0.4
0.5
0.63
0.16
0.2
0.25
0.32
0.4
0.5
0.63
0.2
0.25
0.32
0.4
0.5
0.63
0.25
0.32
0.4
0.5
0.63
0.32
0.4
0.5
0.63
0.4
0.5
0.63
0.5
0.63
13 16 20 25
50
50
63
63
0.63
K-Characteristic
4
6
10
13
16
20
25
32
40
50
63
In (in A)
4
6
10
13
16
20
25
32
40
50
63
0.5
0.06
0.08
0.14
0.18
0.22
0.28
0.35
0.45
0.56
0.7
0.88
0.5
0.4
0.6
0.1
0.13
0.16
0.2
0.25
0.32
0.4
0.5
0.63
1
0.06
0.08
0.14
0.18
0.22
0.28
0.35
0.45
0.56
0.7
0.88
1
0.4
0.6
0.1
0.13
0.16
0.2
0.25
0.32
0.4
0.5
0.63
2
0.06
0.08
0.14
0.18
0.22
0.28
0.35
0.45
0.56
0.7
0.88
2
0.4
0.6
0.1
0.13
0.16
0.2
0.25
0.32
0.4
0.5
0.63
0.08
0.14
0.18
0.22
0.28
0.35
0.45
0.56
0.7
0.88
0.6
0.1
0.13
0.16
0.2
0.25
0.32
0.4
0.5
0.63
0.14
0.18
0.22
0.28
0.35
0.45
0.56
0.7
0.88
0.1
0.13
0.16
0.2
0.25
0.32
0.4
0.5
0.63
0.18
0.22
0.28
0.35
0.45
0.56
0.7
0.88
0.13
0.16
0.2
0.25
0.32
0.4
0.5
0.63
0.22
0.28
0.35
0.45
0.56
0.7
0.88
0.16
0.2
0.25
0.32
0.4
0.5
0.63
0.28
0.35
0.45
0.56
0.7
0.88
13
0.2
0.25
0.32
0.4
0.5
0.63
0.35
0.45
0.56
0.7
0.88
16
0.25
0.32
0.4
0.5
0.63
0.45
0.56
0.7
0.88
20
0.32
0.4
0.5
0.63
0.56
0.7
0.88
25
0.4
0.5
0.63
0.7
0.88
32
0.5
0.63
0.88
40
3 4 6 10 13 16 20 25 32 40
C-Characteristic
C-Characteristic
D-Characteristic In (in A)
3 4 6 10
50
50
63
63
0.63
D-Characteristic 4
6
D-Characteristic
6
K-Characteristic
10
13
16
20
25
32
40
50
63
In (in A)
0.14
0.18
0.22
0.28
0.35
0.45
0.56
0.7
0.88
6
0.22
0.28
0.35
0.45
0.56
0.7
0.88
10
0.28
0.35
0.45
0.56
0.7
0.88
0.35
0.45
0.56
0.7
0.88
0.45
0.56
0.7
0.88
0.56
0.7
0.88
0.7
0.88
32
0.88
40
10 13 16 20 25 32 40
D-Characteristic
In (in A)
4
6
10
13
16
20
25
32
40
50
63
0.1
0.13
0.16
0.2
0.25
0.32
0.4
0.5
0.63
0.16
0.2
0.25
0.32
0.4
0.5
0.63
0.2
0.25
0.32
0.4
0.5
0.63
0.25
0.32
0.4
0.5
0.63
0.32
0.4
0.5
0.63
0.4
0.5
0.63
0.5
0.63
13 16 20 25
50
50
63
63
0.63
K-Characteristic
4
6
10
13
16
20
25
32
40
50
63
In (in A)
4
6
10
13
16
20
25
32
40
50
63
0.5
0.06
0.08
0.14
0.18
0.22
0.28
0.35
0.45
0.56
0.7
0.88
0.5
0.4
0.6
0.1
0.13
0.16
0.2
0.25
0.32
0.4
0.5
0.63
1
0.06
0.08
0.14
0.18
0.22
0.28
0.35
0.45
0.56
0.7
0.88
1
0.4
0.6
0.1
0.13
0.16
0.2
0.25
0.32
0.4
0.5
0.63
2
0.06
0.08
0.14
0.18
0.22
0.28
0.35
0.45
0.56
0.7
0.88
2
0.4
0.6
0.1
0.13
0.16
0.2
0.25
0.32
0.4
0.5
0.63
0.08
0.14
0.18
0.22
0.28
0.35
0.45
0.56
0.7
0.88
0.6
0.1
0.13
0.16
0.2
0.25
0.32
0.4
0.5
0.63
0.14
0.18
0.22
0.28
0.35
0.45
0.56
0.7
0.88
0.1
0.13
0.16
0.2
0.25
0.32
0.4
0.5
0.63
0.18
0.22
0.28
0.35
0.45
0.56
0.7
0.88
0.13
0.16
0.2
0.25
0.32
0.4
0.5
0.63
0.22
0.28
0.35
0.45
0.56
0.7
0.88
0.16
0.2
0.25
0.32
0.4
0.5
0.63
0.28
0.35
0.45
0.56
0.7
0.88
13
0.2
0.25
0.32
0.4
0.5
0.63
0.35
0.45
0.56
0.7
0.88
16
0.25
0.32
0.4
0.5
0.63
0.45
0.56
0.7
0.88
20
0.32
0.4
0.5
0.63
0.56
0.7
0.88
25
0.4
0.5
0.63
0.7
0.88
32
0.5
0.63
0.88
40
3 4 6 10 13 16 20 25 32 40
C-Characteristic
K-Characteristic
D-Characteristic In (in A)
3 4 6 10
50
50
63
63
28 S800, SMISSLINE with ABB Products | Back-up and Selectivity tables
0.63