Back-up and Selectivity tables S800, SMISSLINE with ABB Products

Back-up and Selectivity tables | S800, SMISSLINE with ABB Products 5. Back-up protection. Fuses NH/Tmax – S400/S450, S800. Upstream: Fuse NH..gL/gG. Upstream. NH gL/gG. Downstream. Icu [kA]. In [A]. 25. 40. 63. 80. 100 125 160 200. S400M/S450M. FS401M/FS451M. FS403M/FS453M. Icn [kA]. 10 all types.
1MB Größe 145 Downloads 798 Ansichten
Technical Catalogue, Version June 2014

Back-up and Selectivity tables S800, SMISSLINE with ABB Products

Content

Back-up protection at 230/400 V

Selectivity at 400/415V

Tmax/Fuse -S800B

5

-S400/S450

5

XT -S800B

5

Selectivity at 400/415V

-S400/S450

5

Tmax -DS400

Tmax/Fuse -DS401

6

XT -DS401

6

S800S

-S60, -S200

7



-S280, -S400

8

-SN201 -S60, -S200

10



-S280, -S400

11

S800C

-S60, S200



-S280, -S400

13 14–15 16

S800B -S200

17

-S400

18

S800B -SN201

19

S800U

20

-S200

21



22

-S280, -S400

68–69

12

-SN201

-S60, -S200

64–67

9

S800N

-SN201

Tmax -S400

Back-up protection at 240 V Tmax/Fuse -S800U

23

Back-up protection at 415 V Tmax -S800

24

XT -S800

24

Back-up protection at 254/440 V S800S, -N

-S400, -S450M

25

Selectivity at 230/400 V Fuse -S400

26

S400 -S400 27–28 S800S -S200

29–34

S800S -S400

35–37

Selectivity at 230/400 V S800N -S200

38–43

-S400

44–46

Selectivity at 400/415 V Tmax -S800S

47–49

-S800N 50–51

Selectivity at 254/440 V S800S -S400M

52–53

S800N -S400M

54–55

Miniature circuit breaker S400M Selectivity to Sace Tmax T1, T2

56–62

Selectivity at 690 V Fuse

-S800 63 Back-up and Selectivity tables | S800, SMISSLINE with ABB Products 3

Back-up and selectivity dates S400/S450, FS401, FS403 and S800 S800N – S400E @ 230/400 V

Supply side

Upstream Char. I cu [kA]

Downstream

Load side

S400E

B

6

In [A] 6 10 13 16 20 25 32 40 36 63

25 36 36 36 36

32 36 36 36 36 36

40 36 36 36 36 36 36

S800N B, C, D 36 50 63 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36

80 36 36 36 36 36 36 36 36 36

100 125 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36

Example 1: With a S800Nominal current 50 A is a Back-up protection till a nominal current of 25 A to a S400 given. The Back-up protection ist till 36 kA. Example 2: There is no Back-up protection between supply side and the load side given. Back-up protection The tables given provide the value (in kA, referring to the breaking capacity) for which the back-up protection among the combination of selected circuit breakers is verified. The tables cover the possible combinations between S800 and those between the above mentioned circuit breakers and the ABB series of modular circuit breakers S400. The values indicated in the tables refer to the voltage: – Vn of 230/400 VAC Upstream Char. Downstream

I cu [kA]

50

S400M S450M

C

25

15

In [A] 0.5 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63

25 T T T T 0.7 0.6 0.5 0.4 0.4 0.4

32 T T T T 2 1.2 0.9 0.5 0.5 0.5 0.5

40 T T T T 4 2 1.1 0.8 0.8 0.8 0.8 0.7 0.7

S800S D 50 50 63 T T T T T T T T T T 4 7 1.8 2.5 1 1.3 1 1.3 1 1.3 1 1.3 1 1.2 1 1.2 0.9 1 1

80 100 125 T T T T T T T T T T T T T T T T T T 9 T T 2.5 3.5 6.7 2.5 3.5 6.7 2.3 3 5.1 2.3 3 5.1 2.1 2.7 4.3 2.1 2.7 4.3 1.7 2.2 3.4 1.7 2.2 3.4 1.4 1.7 2.1 1.6 2.1

Example 1: In this combination is a selectivity switch off till 5.1 kA given. Example 2: There is no selectivity. Selective protection The tables given provide the value (in kA, referring to the breaking capacity) for which the selective protection is verified among the combination of selected circuit breakers. The tables cover the possible combinations between S800 and the ABB series of modular circuit breakers. The values in the table represent the maximum value obtainable of discrimination between supply side circuit breaker and load side circuit breaker referring to the voltage: – Vn of 230/400 VAC

Consulting the back-up table This table provides the value (in kA) for which the back-up protection is ensured between a given combination of circuit ­b reakers. The table covers possible combinations between the S800, Tmax, SMISSLINE MCBs, S60 and S200. Tmax and between SMISSLINE miniature circuit breakers S400/S450. a) If the short-circuit current at the point of installation of the circuit breaker is not greater than the nominal breaking capacity of the MCB, an upstream fuse is not needed. If a fuse is fitted upstream for installation reasons, any nominal current may be selected for the fuse. b) If the short-circuit current at the point of installation of the circuit breaker is greater than its nominal breaking capacity, the nominal currents of the upstream fuses must not exceed the values specified in the table (back-up protection of the circuit breaker). 4 S800, SMISSLINE with ABB Products | Back-up and Selectivity tables

Back-up protection Fuses NH/Tmax – S400/S450, S800 Upstream: Fuse NH..gL/gG Upstream I cu [kA]

Downstream S400M/S450M FS401M/FS451M FS403M/FS453M S400E/S450E FS401E/FS451E FS403E/FS453E

NH gL/gG

In [A]

25

40

63

Icn [kA] 10

all types

100 100 100 100

80

50

30

20

Icn [kA] 6

all types

100 100

25

15

10



70

80

40

100 125 160 200

Tmax – S800B @ 230/400 V

Downstream S800B

Char.

ln [A]

B, C

32...100

D, K

125*

Upstream

T1

T1

T2

T4

Version

B

C

N

S

H

L

L

V

lcu [kA]

16

25

36

50

70

85

120

200

16

T1

T2

T3

T4

T2

T3

T4

T2

T4

T4

25

36

36

36

36

50

50

50

70

70

85

120

200

25

36

36

36

36

50

50

50

70

70

85

120

200

T2

T4

T4

Sace Tmax – S400 @ 230/400 V T1

T1

T1

T2

T3

T4

T2

T3

T4

T2

T4

Version

B

C

N

N

N

N

S

S

S

H

H

lcu [kA]

16

25

36

36

36

36

50

50

50

70

70

85

120

200

36

36

40

40

40

30

40

40

40

6

16

25

30

36

16

16

16

16

16

16

16

40

40

50

40

50

40

40

10

16

25

30

36

25

40

50

40

50

40

40

40

40

50

40

50

40

40

10

16

25

30

36

25

40

50

40

50

40

40

Upstream Version ln [A]

Downstream S400E/S450E FS401E/FS451E FS403E/FS453E

6…10 B, C 13…63

S400M/S450M FS401M/FS451M C, K FS403M/FS453M

0.5…10

S400M/S450M FS401M/FS451M B, D FS403M/FS453M

6…10

13…63

13…63

16

16

36

36

25

36

36

36

25

36

40

40

36

L

V

Sace XT - DS400 @230/400V Supply side 415 V AC

XT2

XT2

XT2

XT2

Version

N

S

H

V

Load side 240 V AC

ln [A]

lcu [kA]

36

50

70

150

DS401M DS402M

≤ 40

10

36

40

40

40

Supply side 415 V AC

XT1

XT1

XT1/XT3/XT4

XT1/XT3/XT4

XT1/XT4

XT4

XT4

Version

B

C

N

S

H

L

V

Load side 240 V AC

ln [A]

lcu [kA]

18

25

36

50

70

120

150

DS401M

≤ 20

10

18

20

20

20

20

20

20

DS402M

25 to 40

10

10

10

10

10

10

10

10

XT – S800B @ 230/400 V Upstream Downstream S800B

Char.

ln [A]

B, C

32...100

D, K

125*

XT1

XT1

Version

B

C

lcu [kA]

18

25

120

120

18

25

36

36

36

36

50

50

50

50

70

70

70

120

120

150

150

18

25

36

36

36

36

50

50

50

50

70

70

70

120

120

150

150

XT3

XT4

XT1

XT2

XT3

XT4

XT1

XT2

XT4

16

XT1

XT2

XT3

XT4

XT1

XT2

N

XT3

XT4

XT1

S

36

XT2

XT4

XT2

H

50

XT4

XT2

L

70

XT4 V

150

Sace XT – S400 @ 230/400 V XT1

Upstream Version Downstream FS400E S400E S450E FS400M S400M S450M FS400M S400M S450M

ln [A] B, C C, K B, D

6…10 13…63 0.5…10 13…63 6…10 13…63

XT2

Version

B

C

N

lcu [kA]

18

25

36

S 50 36

6

18

25

30

36

10

18

25

30

36

10

18

25

30

36

16

36

30

36

36

30

50

36

30

50

16

40

30

40

30

40

30

40

36 25

XT4

XT2

XT4

L

V

70

120

150

40

36 25

XT2

H

25

40

70

40 25

40

60

40

85 40

70 60

40

60 60

40

85 40

85 40

40

60

40

85 40

60

40

Selectivity limits are specified in kA

Back-up and Selectivity tables | S800, SMISSLINE with ABB Products 5

Back-up protection Fuses – MCB – DS401, DS451 MCB -MCB @ 240 V Supply side

25gG

40gG

50gG

63gG

80gG

100gG

Char. Icu [kA]

Load side

In [A]

DS401 DS451

B, C

10

2…40

35

25

20

15

10

10

DS401M/ DS402M DS451M

B, C

10

2…40

35

25

20

15

10

10

MCCB @ 415 V – MCB/RCBO @ 240 V Supply side 1 Char. Load side

Version Icu [kA]

T1 C 25

T1

16

16

16

T2 N 36

T3

T2

T3 S 50

T2 H 70

T2 L 85

25

25

16

16

25

25

16

16

In [A] 2…25

DS401 DS451

B, C, D, K

10

DS401M/ DS402M DS451M

B, C

10

1

T1 B 16

25

32, 40

16

2…25 16

16

16 16

25 16

32, 40

25 16

25 16

16

16 16

Supply side circuit-breaker 4P (load side circuit branched between one phase and the neutral

6 S800, SMISSLINE with ABB Products | Back-up and Selectivity tables

Back-up protection S800S – S60, -S200, -S200M, -S200P S800S – S60 @ 230/400 V

S800S – S200M @ 230/400 V

Upstream Char. Icu [kA]

Downstream

S60

C

In [A] 2 4 6 8 10 13 16 20 25 32 40 50 63

6

25 50 50 50 50 50 50 50

32 50 50 50 50 50 50 50 50

40 50 50 50 50 50 50 50 50 50

S800S B, C, D, K 50 50 63 25 18 25 18 25 18 25 18 25 18 25 18 25 18 25 18 25 18 25 18 18

Upstream Char. 80 15 15 15 15 15 15 15 15 15 15 15 15

100 125 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15

Icu [kA]

Downstream

S200M

B

15

Upstream Icu [kA]

Downstream

S200

B

In [A] 6 10 13 16 20 25 32 40 50 63

10

25 50 50 50 50

32 50 50 50 50 50

40 50 50 50 50 50 50

Upstream Char. Icu [kA]

Downstream

S200

C

10

In [A] 0.5…6 8 10 13 16 20 25 32 40 50 63

25 50 50 50 50 50

32 50 50 50 50 50 50

40 50 50 50 50 50 50 50

S800S B, C, D, K 50 50 63 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50

S800S B, C, D, K 50 50 63 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50

100 125 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50

C

15

In [A] 0.5…16 20 25 32 40 50 63

25 50

32 50 50

40 50 50 50

S800S B, C, D, K 50 50 63 50 50 50 50 50 50 50 50 50

80 50 50 50 50 50 50

100 125 50 50 50 50 50 50 50 50 50 50 50 50 50 50

80 50 50 50 50 50 50

100 125 50 50 50 50 50 50 50 50 50 50 50 50 50 50

80 50 50 50 50 50 50

100 125 50 50 50 50 50 50 50 50 50 50 50 50 50 50

80 50 50 50 50 50 50

100 125 50 50 50 50 50 50 50 50 50 50 50 50 50 50

S800S – S200P @ 230/400 V Upstream Char. Icu [kA]

Downstream

25 B 15

100 125 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50

40 50 50 50

Icu [kA]

Downstream

S200P

80 50 50 50 50 50 50 50 50 50 50

32 50 50

Upstream

S200M

80 50 50 50 50 50 50 50 50 50

25 50

Char.

S800S – S200 @ 230/400 V Char.

In [A] 6…16 20 25 32 40 50 63

S800S B, C, D, K 50 50 63 50 50 50 50 50 50 50 50 50

In [A] 6…16 20 25 32 40 50 63

25 50

32 50 50

40 50 50 50

Upstream Char. Icu [kA]

Downstream

25 S200P

C 15

In [A] 0.5…16 20 25 32 40 50 63

25 50

32 50 50

40 50 50 50

S800S B, C, D, K 50 50 63 50 50 50 50 50 50 50 50 50

S800S B, C, D, K 50 50 63 50 50 50 50 50 50 50 50 50

S800S – S200L @ 230/400 V Upstream Char. Icu [kA]

Downstream

S200L

C

6

In [A] 6...8 10 13 16 20 25 32 40

25 50 50 50 50

32 50 50 50 50 50

40 50 50 50 50 50 50

S800S B, C, D, K 50 50 63 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50

80 50 50 50 50 50 50 50 50

100 125 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50

Backup limit values indicated in kA

Back-up and Selectivity tables | S800, SMISSLINE with ABB Products 7

Back-up protection S800S – S280, -S400E, -S400M S800S – S400E @ 230/400 V

S800S – S280 @ 230/400 V Upstream Char. Icu [kA]

Downstream

10

S280

B

25

15 10

In [A] 6 10 13 16 20 25 32 40 50 63

25 50 50 50 50

32 50 50 50 50 50

40 50 50 50 50 50 50

Upstream Char. Icu [kA]

Downstream

10

S280

C

25

15 10

In [A] 3 4 6 8 10 13 16 20 25 32 40 50 63

25 50 50 50 50 50 50 50

32 50 50 50 50 50 50 50 50

40 50 50 50 50 50 50 50 50 50

Upstream Char. Icu [kA]

Downstream

10

S280

K, Z

25

15 10

In [A] 3 4 6 8 10 13 16 20 25 32 40 50 63

25 50 50 50 50 50 50 50

32 50 50 50 50 50 50 50 50

40 50 50 50 50 50 50 50 50 50

S800S B, C, D, K 50 50 63 50 50 25 20 25 20 25 20 25 20 25 20 25 20 20

S800S B, C, D, K 50 50 63 50 50 50 50 50 50 25 20 25 20 25 20 25 20 25 20 25 20 25 20 20

S800S B, C, D, K 50 50 63 50 50 50 50 50 50 25 20 25 20 25 20 25 20 25 20 25 20 25 20 20

Upstream Char. 80 50 16 16 16 16 16 16 16 16

100 125 50 50 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16

Icu [kA]

Downstream

Icn [kA] 6

S400E

B

In [A] 6 10 13 16 20 25 32 40 50 63

25 50 50 50 50

32 50 50 50 50 50

40 50 50 50 50 50 50

Upstream Char. 80 50 50 50 16 16 16 16 16 16 16 16 16

100 125 50 50 50 50 50 50 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16

Icu [kA]

Downstream

Icn [kA]

6 S400E

C

In [A] 0.5...6 8 10 13 16 20 25 32 40 50 63

25 50 50 50 50 50

32 50 50 50 50 50 50

40 50 50 50 50 50 50 50

S800S B, C, D, K 50 50 63 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50

S800S B, C, D, K 50 50 63 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50

80 50 50 50 50 50 50 50 50 50

100 125 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50

80 50 50 50 50 50 50 50 50 50 50

100 125 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50

80 50 50 50 50 50 50

100 125 50 50 50 50 50 50 50 50 50 50 50 50 50 50

80 50 50 50 50 50 50

100 125 50 50 50 50 50 50 50 50 50 50 50 50 50 50

S800S – S400M @ 230/400 V Upstream 80 50 50 50 16 16 16 16 16 16 16 16 16

100 125 50 50 50 50 50 50 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16

Backup limit values indicated in kA

8 S800, SMISSLINE with ABB Products | Back-up and Selectivity tables

Char. I cu [kA]

Downstream

Icn [kA] S400M S450M FS401M FS403M

B, D

10

In [A] 4*…16 20 25 32 40 50 63

* for B characteristic only Upstream Char. DownI cu [kA] stream I n [A] 50 0.5…2 25 3...20 25 S400M 32 C, K S450M 40 15 50 63

25 50

25 50 50

32 50 50

32 50 50

40 50 50 50

40 50 50 50

S800S B, C, D, K 50 50 63 50 50 50 50 50 50 50 50 50

S800S B, C, D, K 50 50 63 50 50 50 50 50 50 50 50 50

Back-up protection S800S – SN201 S800S – SN201 @ 230/400 V Upstream Char. Icu [kA]

Downstream

SN201

B, D

10

In [A] 6 10 16 20 25 32 40

25 50 50 50

32 50 50 50 50

40 50 50 50 50 50

S800S B, C, D, K 50 50 63 50 50 50 50 50 50 50 50 50 50 50 50 50

80 50 50 50 50 50 50 50

100 125 50 50 50 50 50 50 50 50 50 50 50 50 50 50

S800S B, C, D, K 50 50 63 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50

80 50 50 50 50 50 50 50 50 50

100 125 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50

S800S B, C, D, K 50 50 63 25 18 25 18 25 18 25 18 25 18 25 18 25 18 25 18 18

80 15 15 15 15 15 15 15 15 15

100 125 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15

S800S B, C, D, K 50 50 63 50 50 50 50 50 50 50 50 50 50 50 50 50

80 50 50 50 50 50 50 50

100 125 50 50 50 50 50 50 50 50 50 50 50 50 50 50

S800S B, C, D, K 50 50 63 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50

80 50 50 50 50 50 50 50 50

100 125 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50

S800S – SN201 @ 230/400 V Upstream Char. Icu [kA]

Downstream

SN201

C

10

In [A] 2 4 6 10 16 20 25 32 40

25 50 50 50 50 50

32 50 50 50 50 50 50

40 50 50 50 50 50 50 50

S800S – SN201 L @230/400 V Upstream Char. Icu [kA]

Downstream

SN201 L

B, C

6

In [A] 2 4 6 10 16 20 25 32 40

25 50 50 50 50 50

32 40 40 40 40 40 40

40 25 25 25 25 25 25 25

S800S – SN201 M @ 230/400 V Upstream Char. Icu [kA]

Downstream

SN201 M

B

10

In [A] 6 10 16 20 25 32 40

25 50 50 50

32 50 50 50 50

40 50 50 50 50 50

S800S - SN201 M @ 230/400 V Upstream Char. Icu [kA]

Downstream

SN201 M

C

10

In [A] 2 4 6 10 16 20 25 32

25 50 50 50 50 50

32 50 50 50 50 50 50

40 50 50 50 50 50 50 50

Back-up and Selectivity tables | S800, SMISSLINE with ABB Products 9

Back-up protection S800N – S60, -S200, -S200M, -S200P S800N – S60 @ 230/400 V

S800N – S200M @ 230/400 V

Upstream Char. Icu [kA]

Downstream

S60

C

6

In [A] 2 4 6 8 10 13 16 20 25 32 40 50 63

25 36 36 36 36 36 36 36

32 36 36 36 36 36 36 36 36

40 36 36 36 36 36 36 36 36 36

S800N B, C, D 36 50 63 25 18 25 18 25 18 25 18 25 18 25 18 25 18 25 18 25 18 25 18 18

Upstream Char. 80 15 15 15 15 15 15 15 15 15 15 15 15

100 125 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15

Icu [kA]

Downstream

S200M

B

15

Upstream Icu [kA]

Downstream

S200

B

10

In [A] 6 10 13 16 20 25 32 40 50 63

25 36 36 36 36

32 36 36 36 36 36

40 36 36 36 36 36 36

Upstream Char. Icu [kA]

Downstream

S200

C

10

In [A] 0.5…6 8 10 13 16 20 25 32 40 50 63

25 36 36 36 36 36

32 36 36 36 36 36 36

40 36 36 36 36 36 36 36

S800N B, C, D 36 50 63 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36

S800N B, C, D 36 50 63 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36

100 125 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36

100 125 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36

C

15

Upstream Char. Icu [kA]

Downstream

S200L

C

6

In [A] 6...8 10 13 16 20 25 32 40

25 36 36 36 36

32 36 36 36 36 36

40 36 36 36 36 36 36

S800N B, C, D 36 50 63 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36

80 36 36 36 36 36 36 36 36

100 125 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36

Backup limit values indicated in kA

10 S800, SMISSLINE with ABB Products | Back-up and Selectivity tables

In [A] 0.5…16 20 25 32 40 50 63

25 36

32 36 36

40 36 36 36

S800N B, C, D 36 50 63 36 36 36 36 36 36 36 36 36

80 36 36 36 36 36 36

100 125 36 36 36 36 36 36 36 36 36 36 36 36 36 36

80 36 36 36 36 36 36

100 125 36 36 36 36 36 36 36 36 36 36 36 36 36 36

80 36 36 36 36 36 36

100 125 36 36 36 36 36 36 36 36 36 36 36 36 36 36

80 36 36 36 36 36 36

100 125 36 36 36 36 36 36 36 36 36 36 36 36 36 36

S800N – S200P @ 230/400 V Upstream Char. Icu [kA]

Downstream S200P

B

25

In [A] 6…16 20 25 32 40 50 63

25 36

32 36 36

40 36 36 36

Upstream Char. Icu [kA]

Downstream S200P

C

25

15

S800N – S200L @ 230/400 V

40 36 36 36

Icu [kA]

Downstream

15 80 36 36 36 36 36 36 36 36 36 36

32 36 36

Upstream

S200M

80 36 36 36 36 36 36 36 36 36

25 36

Char.

S800N – S200 @ 230/400 V Char.

In [A] 6…16 20 25 32 40 50 63

S800N B, C, D 36 50 63 36 36 36 36 36 36 36 36 36

In [A] 0.5…16 20 25 32 40 50 63

25 36

32 36 36

40 36 36 36

S800N B, C, D 36 50 63 36 36 36 36 36 36 36 36 36

S800N B, C, D 36 50 63 36 36 36 36 36 36 36 36 36

Back-up protection S800N – S280, -S400E, -S400M S800N – S280 @ 230/400 V

S800N – S400E @ 230/400 V

Upstream Char. Icu [kA]

Downstream

10

S280

B

25

15 10

In [A] 6 10 13 16 20 25 32 40 50 63

25 36 36 36 36

32 36 36 36 36 36

40 36 36 36 36 36 36

Upstream Char. Icu [kA]

Downstream

10

S280

C

25

15 10

In [A] 3 4 6 8 10 13 16 20 25 32 40 50 63

25 36 36 36 36 36 36 36

32 36 36 36 36 36 36 36 36

40 36 36 36 36 36 36 36 36 36

Upstream Char. Icu [kA]

Downstream

10

S280

K, Z

25

15 10

In [A] 3 4 6 8 10 13 16 20 25 32 40 50 63

25 36 36 36 36 36 36 36

32 36 36 36 36 36 36 36 36

40 36 36 36 36 36 36 36 36 36

S800N B, C, D 36 50 63 36 36 25 20 25 20 25 20 25 20 25 20 25 20 20

S800N B, C, D 36 50 63 36 36 36 36 36 36 25 20 25 20 25 20 25 20 25 20 25 20 25 20 20

S800N B, C, D 36 50 63 36 36 36 36 36 36 25 20 25 20 25 20 25 20 25 20 25 20 25 20 20

Upstream Char. 80 36 16 16 16 16 16 16 16 16

100 125 36 36 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16

Icu [kA]

Downstream

Icn [kA]

S400E

B

6

In [A] 6 10 13 16 20 25 32 40 50 63

25 36 36 36 36

32 36 36 36 36 36

40 36 36 36 36 36 36

Upstream Char. 80 36 36 36 16 16 16 16 16 16 16 16 16

100 125 36 36 36 36 36 36 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16

Icu [kA]

Downstream

Icn [kA]

S400E

C

6

In [A] 0.5...6 8 10 13 16 20 25 32 40 50 63

25 36 36 36 36 36

32 36 36 36 36 36 36

40 36 36 36 36 36 36 36

S800N B, C, D 36 50 63 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36

S800N B, C, D 36 50 63 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36

80 36 36 36 36 36 36 36 36 36

100 125 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36

80 36 36 36 36 36 36 36 36 36 36

100 125 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36

80 36 36 36 36 36 36

100 125 36 36 36 36 36 36 36 36 36 36 36 36 36 36

80 36 36 36 36 36 36

100 125 36 36 36 36 36 36 36 36 36 36 36 36 36 36

S800N – S400M @ 230/400 V Upstream 80 36 36 36 16 16 16 16 16 16 16 16 16

100 125 36 36 36 36 36 36 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16

Char. I cu [kA]

Downstream

Icn [kA] S400M S450M FS401MB FS403MB

B, D

10

In [A] 4*…16 20 25 32 40 50 63

25 36

32 36 36

40 36 36 36

S800N B, C, D 36 50 63 36 36 36 36 36 36 36 36 36

* for B characteristic only Upstream Char. I cn [kA]

Downstream

50 25 S400M S450M FS401MC FS451MC

C, K

15

I n [A] 0.5...2 3...20 25 32 40 50 63

25 36 36

32 36 36

40 36 36 36

S800N B, C, D 36 50 63 36 36 36 36 36 36 36 36 36

Backup limit values indicated in kA

Back-up and Selectivity tables | S800, SMISSLINE with ABB Products 11

Back-up protection S800N – SN201 S800N – SN201 @ 230/400 V Upstream Char. Icu [kA]

Downstream

SN201

B, D

10

In [A] 6 10 16 20 25 32 40

25 36 36 36

32 36 36 36 36

40 36 36 36 36 36

S800N B, C, D 36 50 63 36 36 36 36 36 36 36 36 36 36 36 36 36

80 36 36 36 36 36 36 36

100 125 36 36 36 36 36 36 36 36 36 36 36 36 36 36

S800N B, C, D 36 50 63 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36

80 36 36 36 36 36 36 36 36 36

100 125 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36

S800N B, C, D 36 50 63 25 18 25 18 25 18 25 18 25 18 25 18 25 18 25 18 18

80 15 15 15 15 15 15 15 15 15

100 125 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15

S800N B, C, D 36 50 63 36 36 36 36 36 36 36 36 36 36 36 36 36

80 36 36 36 36 36 36 36

100 125 36 36 36 36 36 36 36 36 36 36 36 36 36 36

S800N B, C, D 36 50 63 36 36 36 36 36 36 36 36 36 36 36 36 36 36

80 36 36 36 36 36 36 36

100 125 36 36 36 36 36 36 36 36 36 36 36 36 36 36

S800N – SN201 @ 230/400 V Upstream Char. Icu [kA]

Downstream

SN201

C

10

In [A] 2 4 6 10 16 20 25 32 40

25 36 36 36 36 36

32 36 36 36 36 36 36

40 36 36 36 36 36 36 36

S800N – SN201L @ 230/400 V Upstream Char. Icu [kA]

Downstream

SN201 L

B, C

6

In [A] 2 4 6 10 16 20 25 32 40

25 36 36 36 36 36

32 36 36 36 36 36 36

40 25 25 25 25 25 25 25

S800N – SN201M @ 230/400 V Upstream Char. Icu [kA]

Downstream

SN201 M

B

10

In [A] 6 10 16 20 25 32 40

25 36 36 36

32 36 36 36 36

40 36 36 36 36 36

S800N – SN201M @230/400 V Upstream Char. Icu [kA]

Downstream

SN201 M

C

10

In [A] 2 4 6 10 16 20 25

25 36 36 36 36 36

32 36 36 36 36 36 36

40 36 36 36 36 36 36 36

12 S800, SMISSLINE with ABB Products | Back-up and Selectivity tables

Back-up protection S800C – S60, -S200, -S200M, -S200P S800C – S60 @ 230/400 V

S800C – S200M @ 230/400 V

Upstream Char. Icu [kA]

Downstream

S60

C

6

In [A] 2 4 6 8 10 13 16 20 25 32 40 50 63

25 25 25 25 25 25 25 25

32 25 25 25 25 25 25 25 25

40 25 25 25 25 25 25 25 25 25

S800C B, C, D 25 50 63 25 18 25 18 25 18 25 18 25 18 25 18 25 18 25 18 25 18 25 18 18

Upstream Char. 80 15 15 15 15 15 15 15 15 15 15 15 15

100 125 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15

Icu [kA]

Downstream

S200M

B

15

Upstream Icu [kA]

Downstream

S200

B

10

In [A] 6 10 13 16 20 25 32 40 50 63

25 25 25 25 25

32 25 25 25 25 25

40 25 25 25 25 25 25

Upstream Char. Icu [kA]

Downstream

S200

C

10

In [A] 0.5…6 8 10 13 16 20 25 32 40 50 63

25 25 25 25 25 25

32 25 25 25 25 25 25

40 25 25 25 25 25 25 25

S800C B, C, D 25 50 63 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25

S800C B, C, D 25 50 63 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25

100 125 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25

100 125 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25

40 25 25 25

Icu [kA]

Downstream

C

15

In [A] 0.5…16 20 25 32 40 50 63

25 25

32 25 25

40 25 25 25

S800C B, C, D 25 50 63 25 25 25 25 25 25 25 25 25

80 25 25 25 25 25 25

100 125 25 25 25 25 25 25 25 25 25 25 25 25 25 25

80 25 25 25 25 25 25

100 125 25 25 25 25 25 25 25 25 25 25 25 25 25 25

80 25 25 25 25 25 25

100 125 25 25 25 25 25 25 25 25 25 25 25 25 25 25

80 25 25 25 25 25 25

100 125 25 25 25 25 25 25 25 25 25 25 25 25 25 25

S800C – S200P @ 230/400 V Upstream Char. Icu [kA]

Downstream S200P

B

25

15 80 25 25 25 25 25 25 25 25 25 25

32 25 25

Upstream

S200M

80 25 25 25 25 25 25 25 25 25

25 25

Char.

S800C – S200 @ 230/400 V Char.

In [A] 6…16 20 25 32 40 50 63

S800C B, C, D 25 50 63 25 25 25 25 25 25 25 25 25

In [A] 6…16 20 25 32 40 50 63

25 25

32 25 25

40 25 25 25

Upstream Char. Icu [kA]

Downstream S200P

C

25

15

In [A] 0.5…16 20 25 32 40 50 63

25 25

32 25 25

40 25 25 25

S800C B, C, D 25 50 63 25 25 25 25 25 25 25 25 25

S800C B, C, D 25 50 63 25 25 25 25 25 25 25 25 25

S800C – S200L @ 230/400 V Upstream Char. Icu [kA]

Downstream

S200L

C

6

In [A] 6...8 10 13 16 20 25 32 40

25 25 25 25 25

32 25 25 25 25 25

40 25 25 25 25 25 25

S800C B, C, D 25 50 63 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25

80 25 25 25 25 25 25 25 25

100 125 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25

Backup limit values indicated in kA

Back-up and Selectivity tables | S800, SMISSLINE with ABB Products 13

Back-up protection S800C – S280, -S400E, -S400M S800C – S280 @ 230/400 V

S800C – S400E @ 230/400 V

Upstream Char. Icu [kA]

Downstream

10

S280

B

25

15 10

In [A] 6 10 13 16 20 25 32 40 50 63

25 25 25 25 25

32 25 25 25 25 25

40 25 25 25 25 25 25

Upstream Char. Icu [kA]

Downstream

10

S280

C

25

15 10

In [A] 3 4 6 8 10 13 16 20 25 32 40 50 63

25 25 25 25 25 25 25 25

32 25 25 25 25 25 25 25 25

40 25 25 25 25 25 25 25 25 25

Upstream Char. Icu [kA]

Downstream

10

S280

K, Z

25

15 10

In [A] 3 4 6 8 10 13 16 20 25 32 40 50 63

25 25 25 25 25 25 25 25

32 25 25 25 25 25 25 25 25

40 25 25 25 25 25 25 25 25 25

S800C B, C, D 25 50 63 25 25 25 20 25 20 25 20 25 20 25 20 25 20 20

S800C B, C, D 25 50 63 25 25 25 25 25 25 25 20 25 20 25 20 25 20 25 20 25 20 25 20 20

S800C B, C, D 25 50 63 25 25 25 25 25 25 25 20 25 20 25 20 25 20 25 20 25 20 25 20 20

Upstream Char. 80 25 16 16 16 16 16 16 16 16

100 125 25 25 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16

Icu [kA]

Downstream

Icn [kA]

S400E

B 6

In [A] 6 10 13 16 20 25 32 40 50 63

25 25 25 25 25

32 25 25 25 25 25

40 25 25 25 25 25 25

Upstream Char. 80 25 25 25 16 16 16 16 16 16 16 16 16

100 125 25 25 25 25 25 25 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16

80 25 25 25 16 16 16 16 16 16 16 16 16

100 125 25 25 25 25 25 25 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16

Backup limit values indicated in kA

14 S800, SMISSLINE with ABB Products | Back-up and Selectivity tables

Icu [kA]

Downstream

Icn [kA]

S400E

C

6

In [A] 0.5...6 8 10 13 16 20 25 32 40 50 63

25 25 25 25 25 25

32 25 25 25 25 25 25

40 25 25 25 25 25 25 25

S800C B, C, D 25 50 63 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25

S800C B, C, D 25 50 63 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25

80 25 25 25 25 25 25 25 25 25

100 125 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25

80 25 25 25 25 25 25 25 25 25 25

100 125 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25

Back-up protection S800C – S400M S800C – S400M @ 230/400 V Upstream Char. Icu [kA]

Downstream

Icn [kA] S400M S450M

B, D 10

In [A] 4*…16 20 25 32 40 50 63

25 25

32 25 25

40 25 25 25

S800C B, C, D 25 50 63 25 25 25 25 25 25 25 25 25

80 25 25 25 25 25 25

100 125 25 25 25 25 25 25 25 25 25 25 25 25 25 25

80 25 25 25 25 25

100 125 25 25 25 25 25 25 25 25 25 25 25 25

80 25 25 25 25 25

100 125 25 25 25 25 25 25 25 25 25 25 25 25

* for B characteristic only Upstream Char. Icu [kA]

Downstream

25 S400M S450M

C 15

In [A] 3...20 25 32 40 50 63

25 25

32 25

40 25 25

Upstream Char. Icu [kA]

Downstream

25 S400M S450M

K 10

In [A] 3...20 25 32 40 50 63

25 25

32 25

40 25 25

S800C B, C, D 25 50 63 25 25 25 25 25 25 25

S800C B, C, D 25 50 63 25 25 25 25 25 25 25

Backup limit values indicated in kA

Back-up and Selectivity tables | S800, SMISSLINE with ABB Products 15

Back-up protection S800C – SN201 S800C – SN201 @ 230/400 V Upstream Char. Icu [kA]

Downstream

SN201

B, D

10

In [A] 6 10 16 20 25 32 40

25 25 25 25

32 25 25 25 25

40 25 25 25 25 25

S800C B, C, D, K 25 50 63 25 25 25 25 25 25 25 25 25 25 25 25 25

80 25 25 25 25 25 25 25

100 125 25 25 25 25 25 25 25 25 25 25 25 25 25 25

S800C B, C, D, K 25 50 63 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25

80 25 25 25 25 25 25 25 25 25

100 125 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25

S800C B, C, D, K 25 50 63 25 18 25 18 25 18 25 18 25 18 25 18 25 18 25 18 18

80 15 15 15 15 15 15 15 15 15

100 125 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15

S800C B, C, D, K 25 50 63 25 25 25 25 25 25 25 25 25 25 25 25 25

80 25 25 25 25 25 25 25

100 125 25 25 25 25 25 25 25 25 25 25 25 25 25 25

S800C B, C, D, K 25 50 63 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25

80 25 25 25 25 25 25 25 25

100 125 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25

S800C – SN201 @ 230/400 V Upstream Char. Icu [kA]

Downstream

SN201

C

10

In [A] 2 4 6 10 16 20 25 32 40

25 25 25 25 25 25

32 25 25 25 25 25 25

40 25 25 25 25 25 25 25

S800C – SN201L @ 230/400 V Upstream Char. Icu [kA]

Downstream

SN201L

B, C

6

In [A] 2 4 6 10 16 20 25 32 40

25 25 25 25 25 25

32 25 25 25 25 25 25

40 25 25 25 25 25 25 25

S800C – SN201M @ 230/400 V Upstream Char. Icu [kA]

Downstream

SN201M

B

10

In [A] 6 10 16 20 25 32 40

25 25 25 25

32 25 25 25 25

40 25 25 25 25 25

S800C – SN201M @ 230/400 V Upstream Char. Icu [kA]

Downstream

SN201M

C

10

In [A] 2 4 6 10 16 20 25 32

25 25 25 25 25 25

32 25 25 25 25 25 25

40 25 25 25 25 25 25 25

16 S800, SMISSLINE with ABB Products | Back-up and Selectivity tables

Back-up protection S800B – S200 S800B – S200 @ 230/400 V Upstream

S800B B, C, D, K

Char. Icu [kA]

Downstream

S200

B

In [A] 6 10 13 16 20 25 32 40 50 63

10

32 16 16 16 16 16

40 16 16 16 16 16 16

Upstream

63 16 16 16 16 16 16 16 16

80 16 16 16 16 16 16 16 16 16 16

100 125* 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16

S800B B, C, D, K

Char. Icu [kA]

Downstream

S200

50 16 16 16 16 16 16 16

C, D K, Z

10

In [A] 0.5…6 8 10 13 16 20 25 32 40 50 63

32 16 16 16 16 16 16

40 16 16 16 16 16 16 16

50 16 16 16 16 16 16 16 16

63 16 16 16 16 16 16 16 16 16

80 16 16 16 16 16 16 16 16 16 16 16

100 125* 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16

* only S800B-B,C back-up values indicated in kA

S800B – S200M @ 230/400 V Upstream

S800B B, C, D, K

Char. Icu [kA]

Downstream

15 S200M

B

10

In [A] 6 10 13 16 20 25 32 40 50 63

32 16 16 16 16 16

40 16 16 16 16 16 16

Upstream

63 16 16 16 16 16 16 16 16

80 16 16 16 16 16 16 16 16 16 16

100 125* 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16

S800B B, C, D, K

Char. Icu [kA]

Downstream

S200

50 16 16 16 16 16 16 16

C, D K, Z

15

10

In [A] 0.5…6 8 10 13 16 20 25 32 40 50 63

32 16 16 16 16 16 16

40 16 16 16 16 16 16 16

50 16 16 16 16 16 16 16 16

63 16 16 16 16 16 16 16 16 16

80 16 16 16 16 16 16 16 16 16 16 16

100 125* 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16

* only S800B-B,C

Back-up and Selectivity tables | S800, SMISSLINE with ABB Products 17

Back-up protection S800B – S400 S800B – S400E @ 230/400 V Upstream

S800B B, C, D, K

Char. Icu [kA]

Downstream

S400E

B, C

In [A] 6 8 10 13 16 20 25 32 40 50 63

6

32 16 16 16 16 16 16

40 16 16 16 16 16 16 16

50 16 16 16 16 16 16 16 16

63 16 16 16 16 16 16 16 16 16

80 16 16 16 16 16 16 16 16 16 16 16

100 125* 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16

* only S800B-B,C back-up values indicated in kA

S800B – S400M @ 230/400 V Upstream

S800B B, C, D, K

Char. Icu [kA]

Downstream

S400M

B, D

10

In [A] 6** 8** 10 13 16 20 25 32 40 50 63

32 16 16 16 16 16 16

40 16 16 16 16 16 16 16

Upstream

80 16 16 16 16 16 16 16 16 16 16 16

100 125* 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16

Icu [kA]

Downstream

C

10

In [A] 2 3 4 6 8 10 13 16 20 25 32 40 50 63

32 16 16 16 16 16 16 16 16 16

40 16 16 16 16 16 16 16 16 16 16

Upstream

50 16 16 16 16 16 16 16 16 16 16 16

63 16 16 16 16 16 16 16 16 16 16 16 16

80 16 16 16 16 16 16 16 16 16 16 16 16 16 16

100 125* 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16

S800B B, C, D, K

Char. Icu [kA]

Downstream

S400M

63 16 16 16 16 16 16 16 16 16

S800B B, C, D, K

Char.

S400M

50 16 16 16 16 16 16 16 16

K

10

In [A] 0.5..6 8 10 13 16 20 25 32 40 50 63

32 16 16 16 16 16 16

40 16 16 16 16 16 16 16

50 16 16 16 16 16 16 16 16

63 16 16 16 16 16 16 16 16 16

80 16 16 16 16 16 16 16 16 16 16 16

100 125* 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16

* only S800B-B,C ** only S400M-B

18 S800, SMISSLINE with ABB Products | Back-up and Selectivity tables

Back-up protection S800B – SN201 S800B – SN201 @ 230 V (Two-pole circuit-breakers) Upstream

S800B B, C, D, K

Char. Icu [kA]

Downstream

SN201

B, D

10

In [A] 6 10 16 20 25 32 40

32 16 16 16 16

40 16 16 16 16 16

Upstream

C

10

In [A] 2 4 6 10 13 16 20 25 32 40

32 16 16 16 16 16 16 16

40 16 16 16 16 16 16 16 16

Upstream

50 16 16 16 16 16 16 16 16 16

63 16 16 16 16 16 16 16 16 16 16

80 16 16 16 16 16 16 16 16 16 16

100 125* 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16

Icu [kA]

Downstream

B, C

6

In [A] 2 4 6 10 16 20 25 32 40

32 16 16 16 16 16 16

40 16 16 16 16 16 16 16

Upstream

50 16 16 16 16 16 16 16 16

63 16 16 16 16 16 16 16 16 16

80 15 15 15 15 15 15 15 15 15

100 125* 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15

S800B B, C, D, K

Char. Icu [kA]

Downstream

B

10

In [A] 6 10 16 20 25 32 40

32 16 16 16 16

40 16 16 16 16 16

Upstream

50 16 16 16 16 16 16

63 16 16 16 16 16 16 16

80 16 16 16 16 16 16 16

100 125* 16 16 16 16 16 16 16 16 16 16 16 16 16 16

S800B B, C, D, K

Char. Icu [kA]

Downstream

SN201 M

100 125* 16 16 16 16 16 16 16 16 16 16 16 16 16 16

S800B B, C, D, K

Char.

SN201 M

80 16 16 16 16 16 16 16

Icu [kA]

Downstream

SN201 L

63 16 16 16 16 16 16 16

S800B B, C, D, K

Char.

SN201

50 16 16 16 16 16 16

C

10

In [A] 2 4 6 10 16 20 25 32 40

32 16 16 16 16 16 16

40 16 16 16 16 16 16 16

50 16 16 16 16 16 16 16 16

63 16 16 16 16 16 16 16 16 16

80 16 16 16 16 16 16 16 16 16

100 125 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16

* only S800B-B,C back-up values indicated in kA

Back-up and Selectivity tables | S800, SMISSLINE with ABB Products 19

Back-up compliant to IEC 60947-2 S800U – S60, -S200, -S200L, -S200M S800U – S60 @ 230/400 V

S800U – S200L @ 230/400 V

Upstream Char. Icu [kA]

Downstream

S60

C

6

In [A] 2 4 8 10 13 16 20 25 32 40 50 63

25 50 50 50 50 50 50

32 50 50 50 50 50 50 50

40 50 50 50 50 50 50 50 50

S800U K, Z 50 50 63 25 18 25 18 25 18 25 18 25 18 25 18 25 18 25 18 25 18 18

Upstream Char. 80 15 15 15 15 15 15 15 15 15 15 15

100 125 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15

S800U – S200 @ 230/400 V Char.

S200

Icu [kA]

B

10

S200L

C 6

In [A] 6...8 10 13 16 20 25 32 40

25 50 50 50 50

32 50 50 50 50 50

40 50 50 50 50 50 50

In [A] 6 10 13 16 20 25 32 40 50 63

25 50 50 50 50

32 50 50 50 50 50

40 50 50 50 50 50 50

S800U K, Z 50 50 63 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50

Upstream Char. 80 50 50 50 50 50 50 50 50 50

100 125 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50

Icu [kA]

Downstream

S200M

B 15

In [A] 6...16 20 25 32 40 50 63

25 50

32 50 50

40 50 50 50

Upstream Char. Upstream Char. Icu [kA]

Downstream

S200

B

10

80 50 50 50 50 50 50 50 50

100 125 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50

80 50 50 50 50 50 50

100 125 50 50 50 50 50 50 50 50 50 50 50 50 50 50

80 50 50 50 50 50 50

100 125 50 50 50 50 50 50 50 50 50 50 50 50 50 50

S800U – S200M @ 230/400 V

Upstream Downstream

Icu [kA]

Downstream

S800U K, Z 50 50 63 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50

In [A] 0.5...6 8 10 13 16 20 25 32 40 50 63

25 50 50 50 50 50

32 50 50 50 50 50 50

40 50 50 50 50 50 50 50

S800U K, Z 50 50 63 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50

Icu [kA]

Downstream

80 50 50 50 50 50 50 50 50 50 50

100 125 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50

Backup limit values indicated in kA

20 S800, SMISSLINE with ABB Products | Back-up and Selectivity tables

S200M

C 15

In [A] 0.5...16 20 25 32 40 50 63

25 50

32 50 50

40 50 50 50

S800U K, Z 50 50 63 50 50 50 50 50 50 50 50 50

S800U K, Z 50 50 63 50 50 50 50 50 50 50 50 50

Back-up compliant to IEC 60947-2 S800U – S200P S800U – S200P @ 230/400 V Upstream Char. Icu [kA]

Downstream

25 S200P

B 15

In [A] 6...16 20 25 32 40 50 63

25 50

32 50 50

40 50 50 50

Upstream Char. Icu [kA]

Downstream

25 S200P

C 15

In [A] 0.5...16 20 25 32 40 50 63

25 50

32 50 50

40 50 50 50

S800U K, Z 50 50 63 50 50 50 50 50 50 50 50 50

S800U K, Z 50 50 63 50 50 50 50 50 50 50 50 50

80 50 50 50 50 50 50

100 125 50 50 50 50 50 50 50 50 50 50 50 50 50 50

80 50 50 50 50 50 50

100 125 50 50 50 50 50 50 50 50 50 50 50 50 50 50

Backup limit values indicated in kA

Back-up and Selectivity tables | S800, SMISSLINE with ABB Products 21

Back-up compliant to IEC 60947-2 S800U – S280, -S400E, -S400M S800U – S280 @ 230/400 V

S800U – S400E @ 230/400 V

Upstream Char. Icu [kA]

Downstream

10

25

S280

B

15 10

In [A] 6 10 13 16 20 25 32 40 50 63

25 50 50 50 50

32 50 50 50 50 50

40 50 50 50 50 50 50

Upstream Char. Icu [kA]

Downstream

10

S280 25

C

15 10

In [A] 3 4 6 8 10 13 16 20 25 32 40 50 63

25 50 50 50 50 50 50 50

32 50 50 50 50 50 50 50 50

40 50 50 50 50 50 50 50 50 50

Upstream Char. Icu [kA]

Downstream

10

S280 25

K, Z

15 10

In [A] 3 4 6 8 10 13 16 20 25 32 40 50 63

25 50 50 50 50 50 50 50

32 50 50 50 50 50 50 50 50

40 50 50 50 50 50 50 50 50 50

S800U K, Z 50 50 63 50 50 25 20 25 20 25 20 25 20 25 20 25 20 20

S800U K, Z 50 50 63 50 50 25 20 25 20 25 20 25 20 25 20 25 20 25 20 25 20 25 20 20

S800U K, Z 50 50 63 50 50 25 20 25 20 25 20 25 20 25 20 25 20 25 20 25 20 25 20 20

Upstream Char. 80 50 16 16 16 16 16 16 16 16

100 125 50 50 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16

Icu [kA]

Downstream

Icn [kA]

S400E

B

6

In [A] 6 10 13 16 20 25 32 40 50 63

25 50 50 50 50

32 50 50 50 50 50

40 50 50 50 50 50 50

Upstream Char. 80 50 16 16 16 16 16 16 16 16 16 16 16

100 125 50 50 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16

Icu [kA]

Downstream

Icn [kA]

S400E

C

6

In [A] 0.5...6 8 10 13 16 20 25 32 40 50 63

25 50 50 50 50 50

32 50 50 50 50 50 50

40 50 50 50 50 50 50 50

S800U K, Z 50 50 63 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50

S800U K, Z 50 50 63 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50

80 50 50 50 50 50 50 50 50 50

100 125 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50

80 50 50 50 50 50 50 50 50 50 50

100 125 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50

80 50 50 50 50 50 50

100 125 50 50 50 50 50 50 50 50 50 50 50 50 50 50

80 50 50 50 50 50

100 125 50 50 50 50 50 50 50 50 50 50 50 50

80 50 50 50 50 50

100 125 50 50 50 50 50 50 50 50 50 50 50 50

S800U – S400M @ 230/400 V Upstream Char. 80 50 16 16 16 16 16 16 16 16 16 16 16

100 125 50 50 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16

Icu [kA]

Downstream

Icn [kA] S400M S450M

B, D 10

In [A] 4*...16 20 25 32 40 50 63

25 50

32 50 50

40 50 50 50

* only applies to B characteristic

Upstream Char. Icu [kA]

Downstream

25 S400M S450M

C 15

In [A] 3...20 25 32 40 50 63

25 50

32 50

40 50 50

Upstream Char. Icu [kA]

Downstream

25 S400M S450M

K 10

Backup limit values indicated in kA

22 S800, SMISSLINE with ABB Products | Back-up and Selectivity tables

S800U K, Z 50 50 63 50 50 50 50 50 50 50 50 50

In [A] 3...20 25 32 40 50 63

25 50

32 50

40 50 50

S800U K, Z 50 50 63 50 50 50 50 50 50 50

S800U K, Z 50 50 63 50 50 50 50 50 50 50

Back-up compliant to UL 489 Tmax/Fuse – S800U acc. to UL489 Class J Fuse – S800U (1-pole) @ 240 V AC Downstream

Char.

S800U

K, Z

Upstream In [kA] Icu [A] 10...80 30 10...100

Fuse max. 250 30 30

max. 250 30 30

Class J Fuse – S800U (multipole) @ 240 V AC Downstream

Char.

S800U

K, Z

Upstream In [kA] Icu [A] 10...80 50 10...100

Fuse max. 250 50 50

max. 250 50 50

Sace Tmax – S800U (1-pole) @ 240 V AC Upstream Icu [A] Downream S800U

Char. K, Z

30

In [A] 10...80 90...100

T4 N 65 20...250 30 30

T4 S 100 20...250 30 30

T4 H 150 20...250 30 30

T4 L 200 20...250 30 30

T4 V 200 20...250 30 30

T5 N 65 max. 600 30 30

T5 S 100 max. 600 30 30

T5 H 150 max. 600 30 30

T5 L 200 max. 600 30 30

T5 V 200 max. 600 30 30

T4 N 65 20...250 50 50

T4 S 100 20...250 50 50

T4 H 150 20...250 50 50

T4 L 200 20...250 50 50

T4 V 200 20...250 50 50

T5 N 65 max. 600 50 50

T5 S 100 max. 600 50 50

T5 H 150 max. 600 50 50

T5 L 200 max. 600 50 50

T5 V 200 max. 600 50 50

Sace Tmax – S800U (multipole) @ 240 V AC Upstream Icu [kA] Downstream

Char.

S800U

K, Z

50

In [A] 10...80 90...100

Backup limit values indicated in kA

Back-up and Selectivity tables | S800, SMISSLINE with ABB Products 23

Back-up protection Tmax /XT – S800 Tmax – S800 @ 415 V

Downstream

Char.

ln [A]

Upstream

T1

T1

T2

T4

Version

B

C

N

S

H

L

L

V

lcu [kA]

16

25

36

50

70

85

120

200

S800S

B, C, D, K

6…125

50

S800N

B, C, D

6…125

36

S800C

B, C, D, K

10…125

25

T1

T2

36

T3

36

36

T4

T2

36

T3

T4

T2

T4

T4

70

70

85

120

200

50

50

50

70

70

85

120

200

50

50

50

70

70

85

120

200

XT – S800 @ 415 V Upstream

XT1

XT1

Version

B

C

N

S

lcu [kA]

18

25

36

50

Downstream

Char.

ln [A]

S800S

B, C, D, K

6…125

50

S800N

B, C, D

6…125

36

S800C

B, C, D, K

10…125

25

XT1

36

XT2

36

24 S800, SMISSLINE with ABB Products | Back-up and Selectivity tables

XT3

36

XT4

36

XT1

XT2

XT3

XT4

XT1

XT2

XT4

XT2

H

XT4

XT2

XT4

120

120

150

L 70

V

70

70

70

120

120

150

150

50

50

50

50

70

70

70

120

120

150

150

50

50

50

50

70

70

70

120

120

150

150

Back-up protection S800 – S400M S800S – S400M @ 254/440 V

Downstream

S400M S450M

Char.

C, K

Upstream Char. Icu [kA] In [A] 15 0,5…2 10 3…10 13 16 20 25 6 32 40 50 63

25 30 30 30 30

32 30 30 30 30 30

40 30 30 30 30 30 30

S800S B, C, D, K 30 50 63 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30

80 30 30 30 30 30 30 30 30 30

100 125 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30

80 20 20 20 20 20 20 20 20 20

100 125 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20

S800N – S400M @ 254/440 V

Downstream

S400M S450M

Char.

C, K

Upstream Char. Icu [kA] In [A] 15 0,5…2 10 3…10 13 16 20 25 6 32 40 50 63

25 20 20 20 20

32 20 20 20 20 20

40 20 20 20 20 20 20

S800N B, C, D, K 20 50 63 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20

Back-up and Selectivity tables | S800, SMISSLINE with ABB Products 25

Selectivity Fuses gL/gG – S400/S450, FS401/451 In a low voltage distribution system service continuity is much desired. This means, that two or more in series connected overcurrent protection devices should operate selective in case of an overload or a short circuit. Selectivity is achieved, if only the protective device closest to the fault location operates. Selectivity between two protection devices is assured, if the let through energy of the downstream installed protection device does not reach the value of the melting energy of the upstream connected one. In case of a short circuit a selective interruption of the fault current is assured up to the values indicated in the tables. The information is based on the average operating curves of the upstream connected protection devices.

Fuse gL/gG – S400M @ 230/400 V Upstream

Downstream

S400M S450M FS401M FS403M FS451M FS453M

Char.

Fuse gL/gG

ln [A]

16

20

25

35

50

63

80

100

125

160

#2

1

1.2

4

>15 *

>15 *

>15 *

>15 *

>15 *

>15 *

>15 *

3

0.3

0.7

1.2

4.6

6

6

6

6

6

6

4

0.3

0.6

0.9

2.8

6

6

6

6

6

6

6

0.2

0.5

0.8

2

3.3

5.5

6

6

6

6

8

0.2

0.4

0.7

1.7

2.8

4.5

6

6

6

6

10

0.2

0.4

0.7

1.5

2.5

3.5

5

6

6

6

0.7

1.5

2.5

3.5

5

6

6

6

1.3

2

2.9

4.1

6

6

6

20

1.8

2.6

3.5

5

6

6

25

1.8

2.6

3.5

5

6

6

2.2

3

4

6

6

2.5

4

6

6

3.5

5

6

13

B, C

16

32 40 50/63

Fuse gL/gG – S400M @ 230/400 V Upstream

Downstream

Char.

Fuse gL/gG

l n [A]

16

20

25

35

50

63

80

100

125

160

#2

0.3

1.2

4

>15 *

>15 *

>15 *

>15 *

>15 *

>15 *

>15 *

3

0.3

0.7

1.2

4.6

6

6

6

6

6

6

4

0.3

0.6

0.9

2.8

6

6

6

6

6

6

0.7

1.7

3

5.9

6

6

6

6

1.3

2.2

3.6

6

6

6

6

1.7

2.5

4

6

6

6

2.2

3.1

4.6

6

6

16

3.1

4.6

6

6

20

2.6

3.5

6

6

3.5

6

6

5.5

6

6 8 10 S400M S450M

D, K

13

25 32 40

6

50/63

T = total selectivity up to breaking capacity of downstream miniature circuit breaker    Selectivity limits are specified in kA

26 S800, SMISSLINE with ABB Products | Back-up and Selectivity tables

* only applies to IEC/EN 60947-2 characteristics C and K

Selectivity S400/S450 – S400/S450 S400/S450 – S400/S450 @ 230/400 V

S400/S450 – S400/S450 @ 230/400 V

B-Characteristic 6

6

13

16

20

25

32

40

50

63

In (in A)

0.04

0.05

0.06

0.08

0.1

0.13

0.16

0.2

0.25

6

0.05

0.06

10 B-Characteristic

C-Characteristic

10

13

0.08

0.1

0.13

0.16

0.2

0.25

0.08

0.1

0.13

0.16

0.2

0.25

0.1

0.13

0.16

0.2

0.25

0.13

0.16

0.2

0.25

0.16

0.2

0.25

0.2

0.25

32

0.25

40

16 20 25 32 40

4

6

10

13

16

20

25

32

40

50

63

0.075

0.1

0.1

0.2

0.2

0.24

0.3

0.38

0.47

0.1

0.1

0.2

0.2

0.24

0.3

0.38

0.47

0.2

0.2

0.24

0.3

0.38

0.47

0.2

0.24

0.3

0.38

0.47

0.24

0.3

0.38

0.47

0.3

0.38

0.47

0.38

0.47

10 B-Characteristic

In (in A)

13 16 20 25

50

50

63

63

0.47

C-Characteristic

6

10

13

16

20

25

32

40

50

63

In (in A)

0.5

0.02

0.04

0.05

0.06

0.08

0.1

0.13

0.16

0.2

0.25

0.5

4

6

10

0.030 0.045 0.075

13

16

20

25

32

40

50

63

0.1

0.1

0.2

0.2

0.24

0.3

0.38

0.47

1

0.02

0.04

0.05

0.06

0.08

0.1

0.13

0.16

0.2

0.25

1

0.030 0.045 0.075

0.1

0.1

0.2

0.2

0.24

0.3

0.38

0.47

2

0.02

0.04

0.05

0.06

0.08

0.1

0.13

0.16

0.2

0.25

2

0.030 0.045 0.075

0.1

0.1

0.2

0.2

0.24

0.3

0.38

0.47

3

0.04

0.05

0.06

0.08

0.1

0.13

0.16

0.2

0.25

3

0.045 0.075

0.1

0.1

0.2

0.2

0.24

0.3

0.38

0.47

4

0.04

0.05

0.06

0.08

0.1

0.13

0.16

0.2

0.25

4

0.075

0.1

0.1

0.2

0.2

0.24

0.3

0.38

0.47

0.06

0.08

6

0.075

0.1

0.1

0.2

0.2

0.24

0.3

0.38

0.47

0.1

0.2

0.2

0.24

0.3

0.38

0.47

0.2

0.2

0.24

0.3

0.38

0.47

0.2

0.24

0.3

0.38

0.47

0.24

0.3

0.38

0.47

0.3

0.38

0.47

0.38

0.47

6 10

C-Characteristic

C-Characteristic

B-Characteristic In (in A)

0.1

0.13

0.16

0.2

0.25

0.1

0.13

0.16

0.2

0.25

0.13

0.16

0.2

0.25

0.16

0.2

0.25

0.2

0.25

20

0.25

25

13 16 20 25

10 13 16

32

32

40

40

50

50

63

63

0.47

B-Characteristic 6

6

13

16

20

25

32

40

50

63

In (in A)

0.04

0.05

0.06

0.08

0.1

0.13

0.16

0.2

0.25

6

0.06

0.08

0.1

0.13

0.16

0.2

0.25

0.08

0.1

0.13

0.16

0.2

0.25

0.1

0.13

0.16

0.2

0.25

0.13

0.16

0.2

0.25

0.16

0.2

0.25

0.2

0.25

32

0.25

40

10 D-Characteristic

C-Characteristic

10

13 16 20 25 32 40

4

6

10

13

16

20

25

32

40

50

63

0.075

0.1

0.1

0.2

0.2

0.24

0.3

0.38

0.47

10 D-Characteristic

In (in A)

0.1

13

0.2

0.24

0.3

0.38

0.47

0.2

0.24

0.3

0.38

0.47

0.2

0.24

0.3

0.38

0.47

0.24

0.3

0.38

0.47

0.3

0.38

0.47

0.38

0.47

16 20 25

50

50

63

63

0.47

B-Characteristic

C-Characteristic

In (in A)

6

10

13

16

20

25

32

40

50

63

In (in A)

0.5

0.02

0.04

0.05

0.06

0.08

0.1

0.13

0.16

0.2

0.25

0.5

4

6

10

0.030 0.045 0.075

13

16

20

25

32

40

50

63

0.1

0.1

0.2

0.2

0.24

0.3

0.38

0.47

1

0.02

0.04

0.05

0.06

0.08

0.1

0.13

0.16

0.2

0.25

1

0.030 0.045 0.075

0.1

0.1

0.2

0.2

0.24

0.3

0.38

0.47

2

0.02

0.04

0.05

0.06

0.08

0.1

0.13

0.16

0.2

0.25

2

0.030 0.045 0.075

0.1

0.1

0.2

0.2

0.24

0.3

0.38

0.47

3

0.02

4 6 10 13 16 20 25 32 40

0.04

0.05

0.06

0.08

0.1

0.13

0.16

0.2

0.25

3

0.045 0.075

0.1

0.1

0.2

0.2

0.24

0.3

0.38

0.47

0.04

0.05

0.06

0.08

0.1

0.13

0.16

0.2

0.25

4

0.075

0.1

0.1

0.2

0.2

0.24

0.3

0.38

0.47

0.1

0.2

0.2

0.24

0.3

0.38

0.47

0.1

0.2

0.2

0.24

0.3

0.38

0.47

0.2

0.2

0.24

0.3

0.38

0.47

0.2

0.24

0.3

0.38

0.47

0.24

0.3

0.38

0.47

0.3

0.38

0.47

0.38

0.47

0.05

K-Characteristic

K-Characteristic

0.2 0.2

0.06

0.08

0.1

0.13

0.16

0.2

0.25

0.06

0.08

0.1

0.13

0.16

0.2

0.25

0.1

0.13

0.16

0.2

0.25

0.1

0.13

0.16

0.2

0.25

0.13

0.16

0.2

0.25

20

0.16

0.2

0.25

25

0.2

0.25

32

0.25

40

0.08

6 10 13 16

50

50

63

63

0.1

0.47

Back-up and Selectivity tables | S800, SMISSLINE with ABB Products 27

Selectivity S400/S450 – S400/S450 S400/S450 – S400/S450 @ 230/400 V

S400/S450 – S400/S450 @ 230/400 V K-Characteristic

In (in A)

4

6

10

13

16

20

25

32

40

50

63

In (in A)

6

0.06

0.08

0.14

0.18

0.22

0.28

0.35

0.45

0.56

0.7

0.88

6

0.22

0.28

0.35

0.45

0.56

0.7

0.88

10

0.28

0.35

0.45

0.56

0.7

0.88

0.35

0.45

0.56

0.7

0.88

0.45

0.56

0.7

0.88

0.56

0.7

0.88

0.7

0.88

32

0.88

40

10 13 16 20 25 32 40

B-Characteristic

B-Characteristic

D-Characteristic 4

6

10

13

16

20

25

32

40

50

63

0.1

0.13

0.16

0.2

0.25

0.32

0.4

0.5

0.63

0.16

0.2

0.25

0.32

0.4

0.5

0.63

0.2

0.25

0.32

0.4

0.5

0.63

0.25

0.32

0.4

0.5

0.63

0.32

0.4

0.5

0.63

0.4

0.5

0.63

0.5

0.63

13 16 20 25

50

50

63

63

0.63

K-Characteristic

4

6

10

13

16

20

25

32

40

50

63

In (in A)

4

6

10

13

16

20

25

32

40

50

63

0.5

0.06

0.08

0.14

0.18

0.22

0.28

0.35

0.45

0.56

0.7

0.88

0.5

0.4

0.6

0.1

0.13

0.16

0.2

0.25

0.32

0.4

0.5

0.63

1

0.06

0.08

0.14

0.18

0.22

0.28

0.35

0.45

0.56

0.7

0.88

1

0.4

0.6

0.1

0.13

0.16

0.2

0.25

0.32

0.4

0.5

0.63

2

0.06

0.08

0.14

0.18

0.22

0.28

0.35

0.45

0.56

0.7

0.88

2

0.4

0.6

0.1

0.13

0.16

0.2

0.25

0.32

0.4

0.5

0.63

0.08

0.14

0.18

0.22

0.28

0.35

0.45

0.56

0.7

0.88

0.6

0.1

0.13

0.16

0.2

0.25

0.32

0.4

0.5

0.63

0.14

0.18

0.22

0.28

0.35

0.45

0.56

0.7

0.88

0.1

0.13

0.16

0.2

0.25

0.32

0.4

0.5

0.63

0.18

0.22

0.28

0.35

0.45

0.56

0.7

0.88

0.13

0.16

0.2

0.25

0.32

0.4

0.5

0.63

0.22

0.28

0.35

0.45

0.56

0.7

0.88

0.16

0.2

0.25

0.32

0.4

0.5

0.63

0.28

0.35

0.45

0.56

0.7

0.88

13

0.2

0.25

0.32

0.4

0.5

0.63

0.35

0.45

0.56

0.7

0.88

16

0.25

0.32

0.4

0.5

0.63

0.45

0.56

0.7

0.88

20

0.32

0.4

0.5

0.63

0.56

0.7

0.88

25

0.4

0.5

0.63

0.7

0.88

32

0.5

0.63

0.88

40

3 4 6 10 13 16 20 25 32 40

C-Characteristic

C-Characteristic

D-Characteristic In (in A)

3 4 6 10

50

50

63

63

0.63

D-Characteristic 4

6

D-Characteristic

6

K-Characteristic

10

13

16

20

25

32

40

50

63

In (in A)

0.14

0.18

0.22

0.28

0.35

0.45

0.56

0.7

0.88

6

0.22

0.28

0.35

0.45

0.56

0.7

0.88

10

0.28

0.35

0.45

0.56

0.7

0.88

0.35

0.45

0.56

0.7

0.88

0.45

0.56

0.7

0.88

0.56

0.7

0.88

0.7

0.88

32

0.88

40

10 13 16 20 25 32 40

D-Characteristic

In (in A)

4

6

10

13

16

20

25

32

40

50

63

0.1

0.13

0.16

0.2

0.25

0.32

0.4

0.5

0.63

0.16

0.2

0.25

0.32

0.4

0.5

0.63

0.2

0.25

0.32

0.4

0.5

0.63

0.25

0.32

0.4

0.5

0.63

0.32

0.4

0.5

0.63

0.4

0.5

0.63

0.5

0.63

13 16 20 25

50

50

63

63

0.63

K-Characteristic

4

6

10

13

16

20

25

32

40

50

63

In (in A)

4

6

10

13

16

20

25

32

40

50

63

0.5

0.06

0.08

0.14

0.18

0.22

0.28

0.35

0.45

0.56

0.7

0.88

0.5

0.4

0.6

0.1

0.13

0.16

0.2

0.25

0.32

0.4

0.5

0.63

1

0.06

0.08

0.14

0.18

0.22

0.28

0.35

0.45

0.56

0.7

0.88

1

0.4

0.6

0.1

0.13

0.16

0.2

0.25

0.32

0.4

0.5

0.63

2

0.06

0.08

0.14

0.18

0.22

0.28

0.35

0.45

0.56

0.7

0.88

2

0.4

0.6

0.1

0.13

0.16

0.2

0.25

0.32

0.4

0.5

0.63

0.08

0.14

0.18

0.22

0.28

0.35

0.45

0.56

0.7

0.88

0.6

0.1

0.13

0.16

0.2

0.25

0.32

0.4

0.5

0.63

0.14

0.18

0.22

0.28

0.35

0.45

0.56

0.7

0.88

0.1

0.13

0.16

0.2

0.25

0.32

0.4

0.5

0.63

0.18

0.22

0.28

0.35

0.45

0.56

0.7

0.88

0.13

0.16

0.2

0.25

0.32

0.4

0.5

0.63

0.22

0.28

0.35

0.45

0.56

0.7

0.88

0.16

0.2

0.25

0.32

0.4

0.5

0.63

0.28

0.35

0.45

0.56

0.7

0.88

13

0.2

0.25

0.32

0.4

0.5

0.63

0.35

0.45

0.56

0.7

0.88

16

0.25

0.32

0.4

0.5

0.63

0.45

0.56

0.7

0.88

20

0.32

0.4

0.5

0.63

0.56

0.7

0.88

25

0.4

0.5

0.63

0.7

0.88

32

0.5

0.63

0.88

40

3 4 6 10 13 16 20 25 32 40

C-Characteristic

K-Characteristic

D-Characteristic In (in A)

3 4 6 10

50

50

63

63

28 S800, SMISSLINE with ABB Products | Back-up and Selectivity tables

0.63